Instruction and Operating Manual
Smart Valve Positioner
SS2L / SS2R Series
SS2L / SS2R Series
1. Introduction
2
2. Overview
3
11.5.1 Change of Input Signal
3. Specifications
4
11.5.2 Span Adjustment
4. Part Numbering System (Order Code)
5
11.5.3 Zero Adjustment
5. Principle
6
11.5.4 Selecting DA / RA
6. Descriptions of LCD Display and Buttons
6
11.5.5 Selection of Linear, E.Q.%,
7. Installation
7
of Structure
of Operation
11.5 Sub-Parameters
Flow Diagram
Quick Open, User Set (17points)
7.1 Mounting onto Linear Actuator
11.5.6 Split Range Setting
7.2 Mounting onto Rotary Actuator
11.5.7 Valve Shut-Off Setting
8. Air Connections
14
11.5.8 PID-Gain
8.1 SS2L(linear type)
11.5.8.A P-Gain
8.2 SS2R(rotary type)
11.5.8.B I-Gain
9. Electrical Connections
9.1 Terminal
15
Block
9.2 Measuring
11.5.8.C D-Gain
11.5.9 Setting
Output Signal
of Alarm
Limits
11.5.10 Response Speed Adjustment
9.2.1 With mA Loop Calibrator
11.5.11 Moving Display Figure Position
9.2.2 With Multi-meter
11.5.12 Orifice Control Mode
9.3 Wiring
Alarm
Limits
11.5.13 Setting of Output Signal
9.4 Wiring
SPDT Micro
Switches
11.5.14 Setting of Dead Band
9.5 Setting
SPDT Micro
Switches
11.5.15 Control Mode
10. Quick Auto-Calibration
18
12. Maintenance / Service
10.1 Quick Auto-Calibration
12.1 Preliminary Check Points
10.2 Span Adjustment
12.2 Module Parts
10.3 P-Gain Adjustment
12.3 Structure
10.4 Checking Ambient Temperature
12.3 Re-Setting
11. Description of Parameters Flow
20
11.1 Parameters Flow Diagram
of Gauge Block
of Potentiometer
13. Troubleshooting
40
14. Spare Parts
41
11.2 Main Parameters
14.1 SS2L Spare Parts
11.3 Sub-Parameters
14.2 SS2R Spare Parts
11.4 Setting
14.3 List of Spare Parts
Main
Parameters
11.4.1 LOCK ON / OFF
38
15. Dimensions
11.4.2 Display Mode
15.1 SS2L(linear type)
11.4.3 Manual
15.2 SS2R(rotary type)
Mode
11.4.4 Monitor Mode
15.3 SS2R (with 2 x SPDT micro
44
switch)
11.4.5 Auto-Calibration Mode
11.4.5.A Performing Auto-Calibration
11.4.5.B Initializing Parameters
11.4.6 Self-Test Mode
www.conflow.it
1
SS2L / SS2R Series
1. Introduction
1.1 General Information
This instruction and operating manual contains important notices the user should observe for a personal
safety as well as for prevention against damage to property. Notices concerning a personal safety are
highlighted by a safety alert symbol (
).
1.2 General Safety Instructions
This product was delivered out from the factory without any safety problems after a strict quality
management process. In order to maintain this status and ensure a safe operation of this product,
please be sure to read all safety instructions carefully described in this manual and observe safety
information and symbols without exception.
1.3 Correct Usage
①
This product can be used only for purposes specified in these instructions. If they are not
definitely stated in these instructions, the user is fully responsible for all changes and retrofits to
this product.
②
In case of the intrinsically safe product supplied, please make sure to connect this product to the
certified intrinsically safe circuits. These circuits should correspond with the intrinsic safety
parameters indicated on the product nameplate or the certificates. If the circuits do not
correspond with the intrinsic safety parameters on the product nameplate or the certificates, any
safety required for approval can no longer be warranted.
③
This product is the electrostatic sensitive device that may be seriously damaged by voltages
undetectable to a human. These kinds of voltages occur as soon as a electronic component or
an assembly is touched by a person who is not grounded against a static electricity. Damage to a
electronic component as a result of overvoltage cannot usually be detected immediately. It may
become apparent after a long period of operation. Therefore, please make sure to avoid
electrostatic charge.
1.4 Range and Responsibilities of Personnel
①
Qualified personnel should be trained, instructed or authorized in operating and maintaining
products and systems according to the safety regulations for electrical circuits, high pressures
and hazardous atmosphere.
②
For explosion proof products, they should be trained, instructed or authorized in carrying out
work on electrical circuits for hazardous systems.
③
They should be trained or instructed in maintenance and use of proper safety equipment
according to the safety instructions.
④
They should have a good experience to identify risks and avoid potential hazards when working
with these products and systems.
1.5 Transport and Storage
Make sure that damages during delivery are prevented through proper packaging.
Products and replacement parts should be returned in their original packaging. If the original packaging
is no longer available, please ensure that they should be packaged to provide sufficient protection
against transport.
www.conflow.it
2
SS2L / SS2R Series
2. Overview of Structure
This product consists of the following parts.
• Electronic card comprised of microprocessor, HART modem and LCD
• Potentiometer for position feedback
• Gauge block
The followings are descriptions of internal parts without cover.
No.
1
LCD
2
Card cover
3
Gauge block
4
Supply air gauge
5
Out 1 gauge
6
UP, Up button
7
DN, Down button
8
MO, Mode button
9
ENT, Enter button
10
Ground
11
12
www.conflow.it
Description
Cable gland
(or blind plug)
Blind plug
(or cable gland)
13
Air venting hole
14
Body
3
SS2L / SS2R Series
3. Specifications
Input signal
4 - 20 mA @ 24 VDC
Min. / Max. current
3.6 mA / 50mA
Voltage drop (impedance)
Without HART
: 8.7 VDC (435Ω @ 20mA)
With HART
: 9.4 VDC (470Ω @ 20mA)
Stroke
Linear type: 8 - 130mm *
Operating Angle
Rotary type: 25 - 120°
Supply air pressure
1.4 - 7.0 bar (20 - 100 psi)
Output pressure range
0 - 100% of supply air
Air flow capacity
Air consumption
80 ℓ/min = 4.8 Nm3/h = 2.8 scfm (Supply = 1.4 bar)
233 ℓ/min = 14 Nm3/h = 8.2 scfm (Supply = 6 bar)
2.8 ℓ/min = 0.17 Nm3/h = 0.1 scfm (Supply = 1.4 ~ 6 bar)
Operating characteristic
Linearity
< ±0.3% F.S
Sensitivity
<
0.2% F.S
Hysteresis
<
0.2% F.S
Repeatability
<
0.2% F.S
LCD display
4-digit
Response speed
1 - 1000 (Min. 1, Max. 1000)
Scan time
2 ms
Shut-off value
0 - 10%
Valve action
Direct acting (DA) / reverse acting (RA)
Operating temperature
-30 ~ +80℃ (-22 ~ +176℉) **
Pneumatic connections
Rc 1/4 or NPT 1/4
Electrical connections
G 1/2, NPT 1/2 or M20 X 1.5
Explosion proof /
Intrinsically safe (Exia IIC T6) / IP66
protection class
Body material / painting
Aluminum diecast / powder coating
Weight
1.6 kg
* For more than 200mm stroke on request
** Operating temperature of -40℃ on request
www.conflow.it
4
SS2L / SS2R Series
4. Part Numbering System (order code)
4.1 Linear type (SS2L)
SS2L
SS2L - TF
SS2L - EX
SS2L - H
SS2L - P
Linear type
Output position transmitter 4-20 mA
2 x alarm micro switches SPDT
ATEX 94/9/CE IECEx Exia IIC T6
HART Communication
PROFIBUS Communication
Other executions on request
SS2R
SS2R - TF
SS2R - EX
SS2R - H
SS2R - P
Rotary type
Output position transmitter 4-20 mA
2 x alarm micro switches SPDT
ATEX 94/9/CE IECEx Exia IIC T6
HART Communication
PROFIBUS Communication
Other executions on request
5. Principle of Operation
If 4-20 mA input signal is supplied, the micro processor compares input signal with position feedback
and sends control signal to the I/P converting module. Pneumatic signal from the I/P converting module
operates the valve and the valve stays at the desired position.
www.conflow.it
5
SS2L / SS2R Series
6. Descriptions of LCD display and Buttons
① Display of input or output
② Main parameters
③ mA, % display mode
④ Operation of HART
⑤ Up button
⑥ Down button
⑦ Mode button
⑧ Enter button
Press "Mode" button for 5 seconds
ㆍ Quick auto-calibration
Press "Up(▲)" button for 5 seconds
ㆍ P-gain adjustment
Press "Down(▼)" button for 5 seconds
ㆍ Span adjustment
Press "Enter" button for 5 seconds
ㆍ Ambient temperature (℃)
① Display of input or output
② Main parameters
ㆍ mA, %
MODE ↔ RUN ↔ DISP ↔ MAN ↔ MON ↔ AUTO
LOCK ↔ TEST ↔ PARM
③ Display mode
ㆍ Selection of mA, % or in reverse way
④ HART communication
ㆍ HART communication
⑤ Up (
ㆍ UP button
)
⑥ Down (
)
⑦ MO (Mode)
⑧
ENT(Enter)
ㆍ DOWN button
ㆍ Selection of running mode
ㆍ Selection of parameter group or parameter
ㆍ Save of setting values
www.conflow.it
6
SS2L / SS2R Series
7. Installation
7.1 Mounting onto Linear Actuator
7.1.1 Installation of Follower Guide
UNIWORLD and HYGIENIC Series
PIN LEVER BRACKET
HP60 Series
SCREWS
PIN LEVER BRACKET
7.1.2 Installation of Feedback Lever and Mounting Bracket
Mounting bracket for SS2L positioned is designed to support IEC 60534-6-1.
www.conflow.it
1
Mounting bracket
2
Screws
3
Feedback lever
4
SS2L positioned
5
Feedback pin
7
SS2L / SS2R Series
7.1.3 Mounting onto Cast Yoke or Pillar Yoke
< Cast yoke type >
< Pillar yoke type >
① Cast yoke
② Mounting bracket
③ Screws
④ U-bolts
⑤ Pillar yoke
on request
7.1.4 Mounting onto Other Kind of Cast Yoke
① Cast yoke
② Mounting bracket
③ Screws
www.conflow.it
8
SS2L / SS2R Series
7.1.5. Mounting Diagram
“A” Type
Feedback Levers
30
"A" type: 8 ~ 30mm stroke
“B” Type
"B" type: 8 ~ 70mm stroke standard
65
"C" type: 8 ~ 130mm stroke
“C” Type
"D" type: 80 ~ 200mm stroke
130
7.1.6 Installation of Feedback Pin Follower Guide
www.conflow.it
9
SS2L / SS2R Series
7.1.7 Standard Installation
①
Supply air directly to the actuator, adjust the air filter regulator and set air when the valve
reaches to 50% stroke.
②
Install the feedback lever horizontally at 50% stroke position.
③
If the feedback lever is not installed horizontally, move the mounting bracket up and down little
by little so that it can be positioned horizontally.
④
Fix the mounting bracket with screws.
⑤
Connect air lines between the position and the actuator.
⑥
Supply air to the positioned and perform auto-calibration by pushing Mode button for 5
seconds.
⑦
The operating angle from 0% to 100% stroke should be within the range of 30°. In case of the
over-range of 30°, move the valve stem pin left and right and make the operating angle stay
within 30°.
① Be sure to install the air filter regulator
before the positioned
and
check a supply air pressure required to move the valve.
② If the operating
range of
-30°
angle of
to
the SS2L positioner
is out
of
the
+30°, MONT is shown on LCD during auto-
calibration. Take action as advised in the above
⑦
and
at
12mA
get
the
SS2L feedback
lever
positioned
horizontally
(50%). See
11.4.6. MONT.
www.conflow.it
10
SS2L / SS2R Series
7.2 Mounting onto Rotary Actuator
7.2.1 The SS2R positioned supports NAMUR mounting standard (VDI/VDE 3835, IEC 60534-6-2).
① SS2R positioner
② Multi-size bracket
③ Rotary actuator
ⓐ Assemble the multi-size bracket to the positioner with 4 pcs M6 screw.
ⓑ Mount the positioned onto the actuator with 4 pcs M5 screw.
ⓒ Connect air lines between the positioned and the actuator.
ⓓ Perform auto-calibration by pushing MODE button for 5 seconds.
Be sure to install the air filter regulator AFR80 before the positioned
and
check a supply air pressure required to move the valve.
www.conflow.it
11
SS2L / SS2R Series
7.2.2 Mounting with Fork Lever Type
① SS2R positioner
② Multi-size bracket
③ Rotary actuator
④ Fork lever
⑤ Positioner feedback lever
7.2.3 Position of Fork Lever
Clockwise movement
Counter-clockwise Movement
www.conflow.it
12
B
SS2L / SS2R Series
C
7.2.4 Re-assembling Multi-size Bracket according to Rotary Actuator
L
H
D
E
L
F
(mm)
H
L
(mm)
1
(mm)
2
3
H
(mm)
80
20
130
20
80
30
130
30
80
50
130
50
DRAWN
NAME
Kim. K. W
CHECKED
Ko. S. W
APPROVED
Ko. S. Y
DATE
5
4
TITLE :
POWER- GENEX
ht t p:/ / www.power - genex.com
SIGNATURE
PROJ :
SCALE : 1:2
SIZE
,
QUANTITY
DIMENSION : mm
SHEET 1 OF 1
Check L and H on the actuator and re-assemble the multi-size bracket to fit your actuator
mounting configuration.
www.conflow.it
13
PRODUCT NAME :
3r d
MODEL :
: A3
DWG NO.
AUTOMA A
SS2L / SS2R Series
8. Air Connections
① Be sure to install the air filter regulator before the positioner.
② Supply air should not contain water, oil or moisture.
③ It is recommended to set a supply air pressure 10% higher than the actual operating
pressure of the actuator.
8.1 SS2L (linear type)
8.2 SS2R (rotary type)
www.conflow.it
14
SS2L / SS2R Series
9. Electrical Connections
①
Be sure to supply the rated voltage and current stated on this manual. Otherwise, it
may cause a serious damage or malfunctions.
②
Check polarity of + and – exactly and connect wires.
③
When it is necessary to open the positioner cover at a humid place, more attention is
required. It may cause a serious damage or malfunctions.
9.1 Terminal Block
1
Micro Switch
1, 2+
4-20mA input signal
2
4-20mA input signal
-
3
9
- Alarm limit 2
Ground
11
Switch 1 NO
4
+
4-20mA output signal
12
Switch 1 NC
5
-
4-20mA output signal
13
Switch 1 COM
6
+
Alarm limit 1
14
Switch 2 NO
7
-
Alarm limit 1
15
Switch 2 NC
1
2
3
4
5
6
7
8
9
11
12
13
14
15
16
+
-
F
+
-
+
-
+
-
NO
NC
COM
NO
NC
COM
Input
Alarm limit 1
Ground
Output
Switch 1
Switch 2
Alarm limit 2
www.conflow.it
15
SS2L / SS2R Series
9.2 Measuring Output Signal
Position Transmitter Specifications
9.2.1 With mA loop calibrator
9.2.2 With multi-meter
Output signal
4 – 20mA, 2-wire
Power supply
12 – 30 VDC
Output current limit
30mA DC
Linearity
±0.75% F.S
Operating temperature
-20 ~ +80℃
Zero and span of position feedback (4-20mA output signal) are set automatically during
auto-calibration process.
9.3 Wiring Alarm Limits
24VDC should be supplied for alarm limits.
9.4 Wiring SPDT Micro Switches
Micro Switch Specifications
Type
SPDT
Rating code
10.1A @ 250 VAC
Operating temperature
-25 ~ +85℃
www.conflow.it
16
SS2L / SS2R Series
9.5 Setting SPDT Micro Switches
After auto-calibration process, turn the micro switch cams clockwise slowly and check the contact points.
After checking the contact points of the micro switches at a desired position, fix with screws.
For reference, upper switch 1: No. 11, 12, 13
lower switch 2: No. 14, 15, 16
www.conflow.it
17
SS2L / SS2R Series
10. Quick Auto-Calibration
10.1 Quick Auto-Calibration
Supply 4-20mA input signal and push MODE button for 5 seconds, auto-calibration process will start.
①It
It may take a longer time according to sizes of the control valve and the actuator. Generally, it
will take 2 – 3 minutes with the standard size valve and actuator.
②
If “DATA” on LCD blinks after auto-calibration process, see the error codes on page 20.
In case of a reverse acting actuator, RA is displayed and a countdown
begins.
RA
5→4→3→2→1→END→RUN (auto-calibration is completed)
DA
In case of a direct acting actuator, DA is displayed and a countdown
begins.
10.2 Span Adjustment (SPAN)
Span is set automatically after auto-calibration process. But it can be re-set manually as below, if
necessary.
⇒
⇒
Push DN button for 5 seconds, SPAN
Push ENT button, 100 will blink. Push
If SPAN reaches a desired point, push
will appear.
UP or DN button, change the current
MODE button. RUN mode will start.
value and push ENT button for a
memory saving.
The above is just an example to help
understand how to set Span to 98.5%.
Keep pushing UP/DN button, SPAN will increase or decrease fast. 0.1% will increase or
decrease by pushing a button one time.
www.conflow.it
18
SS2L / SS2R Series
10.3 P-Gain Adjustment (P-GN)
Select LOW,
MIDD
or
HIGH in
GROP-Gain after
selecting NORM, SMAL, or
HARD in Control Mode.
If a hunting
SMAL, or
or an oscillation happens after auto-calibration, select a control
HARD) proper
for
again. Change to HIGH from
from
a valve working
condition
and perform
MIDD in GROP in case of a hunting
MIDD in case of an oscillation problem. If a hunting
mode (NORM,
auto-calibration
problem. Change to LOW
or an oscillation still continues to
happen, select other control mode and set in GROP again.
⇒
Keep
pushing
U button for
seconds, GROP will appear.
Push ENT.
5
⇒
Select HIGH or LOW by pushing UP
or DN button.
If it is necessary to
set PIDGAIN, keep
pushing UP
button
for
5 seconds
and
push
MODE
button when
GROP is
and
shown. PID will
be shown
push ENT to
set PID values
10.4 Checking Ambient Temperature
Keep pushing ENTER button, an ambient temperature
surrounding the positioned will appear. Note that this ambient
temperature appears only while pushing ENTER button.
www.conflow.it
19
SS2L / SS2R Series
11. Description of Parameters Flow
11.1 Parameters Flow Diagram
www.conflow.it
20
SS2L / SS2R Series
11.2 Main Parameters
Ref.
11.4.2
(P. 24)
Parameter
Description
Function
DISP
DISPLAY
changes the LCD display mode
PVPR
PV % value
shows the current position by %
PVMA
PV mA value
shows the current position by mA
PVPR-SVPR
shows the current position by % and mA by turns at
(automatic turn)
intervals of 1 second
SVPR
Input signal % value
shows the input signal by %
SVMA
Input signal mA value
shows the input signal by mA
PV % value
shows the current position by % in a reverse way
(reversed value)
( Ex. PVPR – 10% PV-R –
Parameter
Description
Function
MAN
MANUAL
operates the valve manually
MSET
MANUAL-SET
operates the valve manually
END
Move to 100%
moves a valve to 100% regardless of input signals
ZERO
Move to 0%
moves a valve to 0% regardless of input signals
STEP
Move by 1%
moves a valve by 1% regardless of input signals
SVPV
PV-R
Ref.
11.4.3
(P. 25)
Ref.
90% )
Parameter
Description
Function
MON
MONITOR
checks the current status of the positioner
11.4.4
CHEK
ERROR CHEK
checks the errors occurred to the positioner
(P. 26)
MILE
Runtime
checks the total valve runtime
PARA
Registry memory values
checks the registry records in memory
Ref.
Parameter
Description
AUTO
AUTO-SET
TUNE
Auto-calibration
performs auto-calibration
REST
RESET
returns to the factory settings
Ref.
Parameter
Description
Function
11.4.6
PARM
Sub-parameters
see the parameters on next page
Ref.
Parameter
Description
Function
TEST
TEST MODE
tests the positioner
TIME
STEP 간 시간
STP1
STEP1
STP2
STEP2
11.4.5
(P. 27)
11.4.7
(P. 27)
STP3
Function
performs auto-calibration
and return to the factory
settings
sets the testing interval time
0% → 50% → 100% → 50% → 0% → Repeat
0% → 25% → 50% → 75% → 100% →
75%
1%→→ 50%
10%→→ 25%
20%→… 0%
90%→→
Repeat
100%
STEP3
→ 90% … 20% → 10% → 0% →
Repeat
www.conflow.it
21
SS2L / SS2R Series
11.3 Parameters
11.3.1 Main Parameters
Ref.
Parameter
Description
Function
Default
11.5.1 (P. 30)
INPU
Input signal
4…20mA or 20…4mA
4…20mA
11.5.2 (P. 30)
R / DA
RA / DA
Reverse acting or direct acting
RA
11.5.3 (P. 30)
L / E.Q /
QOPN/USER
Characteristic
11.5.4 (P. 32)
SPAN
Span adjustment
0…100%
100%
11.5.5 (P. 32)
ZERO
Zero adjustment
0…99%
0%
11.5.6 (P. 33)
PID
11.5.7 (P. 35)
Linear, E.Q. % (1:25 or 1:50),Quick open
or User set (17points)
P-GN / I-GN
Proportional
/ Integral
Linear
Auto-set
/ D-GN
/ Differential gain value
CTRL
SPED / SWST / CNLT
See 11.3.3 CTRL
ㆍ
11.5.8 (P. 36)
DEAD
Dead band
0…9.99%
0.5%
11.5.9 (P. 37)
H/PR
FDGN / HBIS
See 11.3.3 H/PR
ㆍ
11.5.10 (P.
38)
C/MD
NORM / HARD /
Standard actuator, strong valve packing friction,
SMAL
small actuator or angle seat valve
11.5.11 (P.
39)
SUB
Sub-Parameters
See 11.3.4 SUB
NORM
ㆍ
11.3.2 CTRL - Parameters (control speed adjustment)
Ref.
Parameter
Description
Function
Default
(P. 35)
SPED
Response speed
1…1000
1000
11.5.7.B (P. 35)
SWST
Slow start
Smooth operation
Auto-set
11.5.7.C
CNTL
Control limit
50…1250
Auto-set
11.5.7.A
(P. 36)
11.3.3 H/PR - Parameter (only for hard friction mode)
Ref.
Parameter
Description
Function
Default
(P. 37)
FDGN
D-gain setting for hard mode
D-Gain setting for hard mode
Auto-set
11.5.9.B (P. 37)
HBIS
BIOS setting for hard mode
Precise BIOS setting
Auto-set
11.5.9.A
11.3.4 SUB - Parameter
Parameter
Description
Function
Default
11.5.11.A
Ref.
(P. 39)
SHUT
Shut-off
0…9.9%
0.3%
11.5.11.B
(P. 40)
FOPN
Full-open
0…9.9%
0.3%
11.5.11.C
(P. 40)
OUT
4…20mA or 20…4mA
4…20mA
11.5.11.D
(P. 40)
SPLT
Split range
4…12mA or 12…20mA
4…20mA
11.5.11.E
(P. 40)
DIGN
Display place
11.5.11.F
(P. 41)
ALAM
Alarm limit low, high
AL1L/AL1H, AL2L/AL2H
0…10%, 90…105%
11.5.11.G
(P. 43)
ICAL
IN4M / IN20
Factory setting
11.5.11.H
(P. 43)
FCAL
FB4M / FB20
sets the values in accordance with
4~20mA input signals
sets the values in accordance with
4~20mA output signals
Output
signal
Movement to one or two decimal
places
www.conflow.it
1
Factory setting
22
SS2L / SS2R Series
11.4 Setting of Main Parameters
The following
abbreviations will be used hereafter.
MODE
MO
UP
ENTER
ENT
DOWN
UP
DN
11.4.1 LOCK ON / OFF
LOCK
ON
① LOCK ON
OFF
: Saves all setting values.
② LOCK OFF : Be sure to LOCK OFF when it is necessary to read or change the
selected parameters and the saved setting values.
③ Quick auto-calibration, Span, P-Gain can be carried out without
LOCK Off (see “10.
Quick Auto-calibration”)
④ LOCK is on unless any input signal is not supplied.
⑤ It is difficult
to read or change under LOCK ON situation.
11.4.2 Display Mode
DISP
PVPR %
PVMA mA
SVPV %/mA
SVPR %
SVMA mA
PV-R %
Selection of mA, % or in reverse way with values as shown
(Ex. Reverse
: 20% shown → 80% shown)
www.conflow.it
23