CP260
2V 6Ah(20hr)
The rechargeable batteries are lead-lead dioxide systems. The dilute sulfuric acid electrolyte is
absorbed by separators and plates and thus immobilized. Should the battery be accidentally
overcharged producing hydrogen and oxygen, special one-way valves allow the gases to escape
thus avoiding excessive pressure build-up. Otherwise, the battery is completely sealed and is,
therefore, maintenance-free, leak proof and usable in any position.
Battery Construction
Component
Positive plate
Negative plate
Container
Cover
Safety valve
Terminal
Separator
Electrolyte
Raw material
Lead dioxide
Lead
ABS
ABS
Rubber
Copper
Fiberglass
Sulfuric acid
Performance Characteristics
General Features
●
●
●
●
●
●
●
●
Absorbent Glass Mat (AGM) technology
for efficient gas recombination of up to
99% and freedom from electrolyte
maintenance or water adding.
Not restricted for air transport-complies
with IATA/ICAO Special Provision A67.
UL-recognized component.
Can be mounted in any orientation.
Computer designed lead, calcium tin alloy
grid for high power density.
Long service life, float or cyclic
applications.
Maintenance-free operation.
Low self discharge.
Dimensions and Weight
Length(mm / inch)
Width(mm / inch)
Height(mm / inch)
Total Height(mm / inch)
Approx. Weight(Kg / lbs)
51 / 2.01
33 / 1.30
99 / 3.90
104 / 4.09
0.44 / 0.97
Nominal Voltage
2V
Number of cell
1
Design Life
5 years
Nominal Capacity 77oF(25oC)
20 hour rate (0.3A, 1.75V)
6Ah
10 hour rate (0.55A, 1.75V)
5.5Ah
5 hour rate (1.04A, 1.75V)
5.2Ah
1 hour rate (4.83A, 1.6V)
4.83Ah
Internal Resistance
5mOhms
Fully Charged battery 77oF(25oC)
Self-Discharge
3% of capacity declined per month at 20oC(average)
Operating Temperature Range
Discharge
-20~60oC
Charge
-10~60oC
Storage
-20~60oC
o
o
90A(5s)
Max. Discharge Current 77 F(25 C)
Short Circuit Current
300A
Charge Methods: Constant Voltage Charge
Cycle use
Maximum charging current
Temperature compensation
Standby use
Temperature compensation
77oF(25oC)
2.30-2.35VPC
2.4A
-5.0mV/oC
2.23-2.27VPC
-3.3mV/oC
Discharge Constant Current (Amperes at 77oF25oC)
End Point
Volts/Cell
1.60V
1.65V
1.70V
1.75V
1.80V
5min 10min 15min 30min
28.7
27.1
25.4
24.0
22.3
19.2
18.2
16.9
15.4
13.7
14.2
13.6
12.9
12.3
11.6
8.19
7.87
7.52
7.15
6.77
1h
3h
5h
10h
20h
4.83
4.66
4.47
4.27
4.07
1.81
1.76
1.70
1.65
1.57
1.09
1.09
1.06
1.04
0.99
0.58
0.58
0.58
0.55
0.53
0.31
0.31
0.30
0.30
0.30
Discharge Constant Power (Watts at 77oF25oC)
End Point
Volts/Cell
1.60V
1.65V
1.70V
1.75V
1.80V
5min 10min 15min 30min 45min
52.4
49.9
47.1
44.7
41.7
34.0
32.5
30.3
27.7
24.7
28.0
26.9
25.8
24.6
23.3
17.2
16.5
15.9
15.2
14.5
12.2
11.8
11.3
10.9
10.4
1h
2h
3h
5h
9.64
9.36
9.02
8.68
8.31
5.24
5.11
4.95
4.79
4.58
3.78
3.69
3.59
3.50
3.34
2.29
2.30
2.26
2.22
2.13
(Note)The above characteristics data are average values obtained within
three charge/discharge cycles not the mimimum values.
page1 of 2
www.vision-batt.com
Current
Charged
Volume
O
Discharge characteristic (25 C)
Voltage
CP260
(%) (xCA)
Voltage(V)
2.0
2V6Ah
Charge characteristic curve
Constant voltage charge characteristic
(0.25CA, 25 oC)
(V)
140
1.7A
120
0.25
100
0.20
6A 4.83A
18A 12A
1.5
1.04A 0.55A 0.3A
80
CHARGED VOLUME
2.50
CHARGE VOLTAGE
2.25
0.15
60
0.10
40
0
1
2
3
5
10
min
20 30
60
2
3
5
10
20 30
20
0.05
0
0
h
2.00
CHARGING CURRENT
1.75
0
Discharge time
2
4
6
8
10
12
14
16
18
20
Charging time (hours)
Relationship between
charging voltage and temperature
Self-discharge characteristic
110
100
2.6
CYC
LE U
Capacity(%)
Voltage (V)
90
2.5
SE
2.4
S TA N
2.3
D BY
80
70
60
USE
2.2
-10
0
10
20
30
Ambient temperature( oC)
40
40
50
0
2
6
8
10
12
14
Storage time: months
16
18
20
100
Capacity(%)
Capacity(%)
4
120
100
80
60
Testing conditions: floating voltage: 2.25 to 2.30V/Cell
ambient temperature: 25 oC(77 oF)
80
60
40
40
20
20
0
1
2
Life(year)
100% D.O.D.
0
3
200
30% Depth of discharge
50% D.O.D.
400
600
800
1000
1200
1400
Number of cycles(cycles)
Temperature effects on float life
Temperature effects on capacity
120
10
2.30V/Cell
100
Capacity (%)
Life(years)
20 oC
Cycle service life in relation to
depth of discharge
Life characteristics of standby use
120
0
30 oC
40 oC
50
1
C
0.05
0 .1 C
0.2C
80
60
1.0C
2 .0 C
3 .0 C
40
20
0.1
10
20
30
40
50
0
-20
60
-10
Temperature( oC)
THE INTERNATIONAL CERTIFICATION NETWORK
ISO9001:2000
MH25860
0
10
20
Temperature( oC)
30
40
G4M19906-9202-E-16
www.vision-batt.com
Shenzhen Center Power Tech. Co., Ltd.
Center Power Industrial Park, Tongfu Industrial District Dapeng Town, 518120 Shenzhen, China
Tel: (+86-755) 8431 8088 Fax: (+86-755) 8431 8038 E-mail:
Copy Right Shenzhen Center Power Technology Co., Ltd (Edition 2011-8)
Page 2 of 2