6V 1.2Ah(20hr)
Overview
The rechargeable batteries are lead-lead dioxide systems. The dilute sulfuric acid electrolyte is
absorbed by separators and plates and thus immobilized. Should the battery be accidentally
overcharged producing hydrogen and oxygen, special oneway valves allow the gases to escape
thus avoiding excessive pressure build-up. Otherwise, the battery is completely sealed and is,
therefore, maintenance-free, leak proof and usable in any position.
Battery Construction
Component
Positive plate
Negative plate
Raw material
Lead dioxide
Lead
Container Cover
ABS
General Features
Safety valve
Terminal
Separator
Electrolyte
Rubber
Copper/Plug
Fiberglass
Sulfuric acid
ABS
Battery Specification
Absorbent Glass Mat (AGM) technology for efficient gas
recombination of up to 99% and freedom from
electrolyte maintenance or water adding.
Not restricted for air transport-complies with IATA/ICAO
Special Provision A67.
UL-recognized component.
Can be mounted in any orientation.
Computer designed lead, calcium tin alloy grid for high
power density.
Long service life, float or cyclic
applications.
Maintenance-free operation.
Low self discharge.
Case and cover available in both standard and flame
retardant ABS.
Dimensions and Weight
Length(mm / inch)
Width(mm / inch)
Height(mm / inch)
Total Height(mm / inch)
Approx. Weight(Kg / lbs)
97 / 3.82
24 / 0.94
52 / 2.05
58 / 2.28
0.31 / 0.68
* Weight deviation: ± 5%
Performance Characteristics
6V
Nominal Voltage
3
Number of cell
5 years
Design Life
Nominal Capacity 77℉(25℃)
20 hour rate (0.06A, 5.25V)
1.2Ah
10 hour rate (0.11A, 5.25V)
1.1Ah
5 hour rate (0.21A, 5.25V)
1.05Ah
1 hour rate (0.82A, 4.8V)
0.82Ah
Internal Resistance
Fully Charged battery 77℉(25℃)
≤50mOhms
Self-Discharge
3% of capacity declined per month at 20℃(average)
Operating Temperature Range
Discharge
-20~60℃
Charge
-10~60℃
Storage
-20~60℃
18A(5s)
Max. Discharge Current 77℉(25℃)
60A
Short Circuit Current
Charge Methods: Constant Voltage Charge 77℉(25℃)
Cycle use
2.40-2.45VPC
Maximum charging current
0.48A
Temperature compensation
-15mV/℃
Standby use
2.23-2.30VPC
Temperature compensation
-10mV/℃
Discharge Constant Current (Amperes at 77oF25oC)
97±1
24±1
End Point
Volts/Cell
5min
10min
1.60V
5.00
3.50
15min
30min
1h
3h
5h
10h
20h
2.50
1.45
0.82
0.36
0.22
0.11
0.06
1.65V
4.71
3.34
2.40
1.39
0.79
0.36
0.22
0.11
0.06
1.70V
4.36
3.12
2.27
1.31
0.75
0.35
0.21
0.11
0.06
1.75V
4.00
2.88
2.11
1.21
0.69
0.33
0.21
0.11
0.06
1.80V
3.55
2.61
1.95
1.08
0.63
0.31
0.21
0.11
0.06
o
o
Discharge Constant Power (Watts at 77 F25 C)
End Point
Volts/Cell
1.60V
ADD TIN
5min 10min 15min
8.80
6.02
4.80
30min
45min
1h
2h
3h
2.75
2.08
1.64
1.00
0.72
5h
0.50
1.65V
7.38
5.73
4.58
2.63
1.99
1.58
0.96
0.69
0.50
1.70V
6.93
5.40
4.33
2.50
1.87
1.47
0.90
0.65
0.48
1.75V
6.44
5.02
4.02
2.34
1.71
1.37
0.83
0.61
0.48
1.80V
5.84
4.56
3.61
2.13
1.52
1.21
0.73
0.54
0.48
(Note)The above characteristics data are average values
obtained within three charge/discharge cycles not the mimimum
values.All data shall be changed without notice,Vision reserves
the right to explain and update the information contained
hereinto.
Shenzhen Center Power Tech.Co.Ltd,.
STOCK CODE: 002733
www.vision-batt.com
6V 1.2Ah(20hr)
Constant voltage charging
characteristic (0.25CA,25 ℃)
(%) (XCA) (V)
6.5
140
6.0
5.5
Voltage(v)
Current
Charged
Volume
Discharge characteristic (25℃)
Voltage
CP612
Shenzhen Center Power
Tech.Co.Ltd,.
120
0.25
100
0.20
5.0
80
4.5
0.15
60
4.0
0.10
40
0
1
2
3
5
10
20 30
60
5
2 3
min
10
20 30
20
0.05
0
0
h
7.5
Charged Volume
7.0
Charge Voltage
6.5
6.0
5.5
0
Charging Current
4
6
2
8
10
Discharge time
14
16
18
20
Charging time (hours)
Relationship between
charging voltage and temperature
Self-discharge characteristic
100
7.8
Capacity(%)
Cycl
7.5
e Us
e
7.2
STANDB
6.9
Y USE
90
80
70
60
6.6
-10
12
50
40
30
20
10
Ambient temperature(℃)
0
40
60
50
0
2
4
6
8
10
12
14
Storage time: months
16
18
20
Cycle service life in relation to
depth of discharge
Life characteristics of Standby use
120
120
100
60
Capacity(%)
80
Testing conditions:floating voltage:2.27 to 2.30V Cell
ambient temperature: 25℃(77oF)
80
60
40
40
20
20
1
0
2
Life(year)
30% Depth of discharge
100% D.O.D. 50% D.O.D.
0
3
200
Temperature effects on float life
400
600
800
1000
Number of cycles(cycles)
1200
1400
Temperature effects on capacit
10
120
100
2.30V Cell
1
Capacity (%)
Capacity(%)
100
C
0.05
0.1C
C
02.
80
60
1.0C
2.0C
40
3.0C
20
0.1
10
20
30
40
50
60
Temperature ( ℃)
Shenzhen Center Power Tech.Co.Ltd,.
-20
-10
0
10
20
30
40
50
Temperature ( ℃)
STOCK CODE: 002733