CP495

4V 9.5Ah(20hr)

The rechargeable batteries are lead-lead dioxide systems. The dilute sulfuric acid electrolyte
is absorbed by separators and plates and thus immobilized. Should the battery be accidentally
overcharged producing hydrogen and oxygen, special one-way valves allow the gases to
escape thus avoiding excessive pressure build-up. Otherwise, the battery is completely sealed
and is, therefore, maintenance-free, leak proof and usable in any position.
Battery Construction
Component

Positive plate

Negative plate

Container

Cover

Safety valve

Terminal

Separator

Electrolyte

Raw material

Lead dioxide



Lead

ABS

ABS

Rubber

Copper

Fiberglass

Sulfuric acid

Performance Characteristics

General Features














Absorbent Glass Mat (AGM) technology
for efficient gas recombination of up to
99% and freedom from electrolyte
maintenance or water adding.
Not restricted for air transport-complies
with IATA/ICAO Special Provision A67.
UL-recognized component.
Can be mounted in any orientation.
Computer designed lead, calcium tin alloy
grid for high power density.
Long service life, float or cyclic
applications.
Maintenance-free operation.
Low self discharge.

Dimensions and Weight
Length(mm / inch)
Width(mm / inch)
Height(mm / inch)
Total Height(mm / inch)
Approx. Weight(Kg / lbs)
* Weight deviation: ± 5%

102 / 4.02
44 / 1.73
95 / 3.74
101 / 3.98
1.10 / 2.43


Nominal Voltage
4V
Number of cell
2
Design Life
5 years
Nominal Capacity 77oF(25oC)
20 hour rate (0.475A, 3.5V)
9.5Ah
10 hour rate (0.9A, 3.5V)
9Ah
5 hour rate (1.7A, 3.5V)
8.5Ah
1 hour rate (6.5A, 3.2V)
6.5Ah
Internal Resistance
≤ 8 mOhms
Fully Charged battery 77oF(25oC)
Self-Discharge
3% of capacity declined per month at 20oC(average)
Operating Temperature Range
Discharge
-20~60oC
Charge
-10~60oC
Storage
-20~60oC
o
o
142.5A(5s)

Max. Discharge Current 77 F(25 C)
Short Circuit Current

475A

Charge Methods: Constant Voltage Charge
Cycle use
Maximum charging current
Temperature compensation
Standby use
Temperature compensation

77oF(25oC)
2.40-2.45VPC
3.8A
-10mV/oC
2.23-2.30VPC
-6.6mV/oC

Discharge Constant Current (Amperes at 77oF25oC)
End Point
Volts/Cell
1.60V
1.65V
1.70V
1.75V
1.80V

5min 10min 15min 30min
38.0

36.0
34.0
31.9
29.7

28.5
27.1
25.7
24.3
22.8

20.0
19.1
18.2
17.3
16.3

11.50
11.00
10.60
10.10
9.53

1h

3h

5h

10h


20h

6.50
6.27
6.02
5.75
5.47

2.67
2.59
2.50
2.40
2.29

1.84
1.80
1.75
1.70
1.64

0.92
0.92
0.91
0.90
0.87

0.482
0.480
0.478

0.475
0.472

Discharge Constant Power (Watts at 77oF25oC)
End Point
Volts/Cell
1.60V
1.65V
1.70V
1.75V
1.80V

5min 10min 15min 30min 45min
66.1
62.0
57.9
53.9
49.9

41.3
38.9
36.5
34.1
31.7

34.2
32.4
30.5
28.6
26.7


20.1
19.1
18.0
17.0
15.9

15.6
14.9
14.1
13.4
12.6

1h

2h

3h

5h

11.8
11.3
10.8
10.3
9.7

7.56
7.33
7.08

6.81
6.51

5.25
5.12
4.98
4.83
4.67

3.54
3.47
3.41
3.33
3.25

(Note)The above characteristics data are average values obtained within
three charge/discharge cycles not the mimimum values.
All data shall be changed without notice,Vision reserves the right to explain
and update the information contained hereinto.

page1 of 2

www.vision-batt.com


4.3

3.3

120


0.25

100

0.20

80

0.15

3.0

(0.25CA,25 oC)

0.10

40
2

1

5

3

20 30

10


60

2 3

min

5

10

20 30

20

0.05

0

0

h

5.0

Charged volume

4.7

Charge voltage


4.3

60
2.7
0

4.0

Charging current

3.7

0

Discharge time

2

4

6

8

10

12

14


16

18

20

Charging time (hours)

Relationship between
charging voltage and temperature
V/12V)

(V/8V)

(V/6V)

(V/4V)

(V/CELL)

Self-discharge characteristic

100

15.6

10.4

7.8


5.2

2.6

90

15.0

10.0

7.5

5.0

2.5

14.4

9.6

7.2

4.8

2.4

13.8

9.2


6.9

4.6

2.3

60

13.2

8.8

6.6

4.4

2.2

50

Capacity(%)

110

-10

0

10
20

30
40
50
Ambient temperature( oC)

80
70

40

60

0

2

4

6

8

10

12
14
16
18
Storage time: months


20

Cycle service life in relation to
depth of discharge

Life characteristics of Standby use
120

120

100

100
Capacity(%)

Capacity(%)

Constant voltage charging
characteristic

(%) (XCA) (V)

3.7

0

4V9.5Ah

140


4.0
Battery voltage(V)

Current

Charged
Volume

O

Discharge characteristic (25 C)

Voltage

CP495

80

60

80
60

40

40

20

20


30% Depth of discharge

0

0

1

2
Life(year)

200

400

3

600

800

1000

1200

1400

Number of cycles(cycles)


Temperature effects on float life

Temperature effects on capacity
120

10

Capacity (%)

Life(years)

100

1

80
60
40
20

0.1

10

20

30

40


50

0

60

-20

-10

0

10

20

30

40

Temperature( oC)

THE INTERNATIONAL CERTIFICATION NETWORK

ISO9001:2008

MH25860

G4M19906-9202-E-16


www.vision-batt.com

Shenzhen Center Power Tech. Co., Ltd.
Center Power Industrial Park, Tongfu Industrial District Dapeng Town, 518120 Shenzhen, China
Tel: (+86-755) 8431 8088 Fax: (+86-755) 8431 8038 E-mail:
Copy Right Shenzhen Center Power Technology Co., Ltd (Edition 2013-4)

Page 2 of 2

50( o C)



×