CP12200

12V 20Ah(20hr)

The rechargeable batteries are lead-lead dioxide systems. The dilute sulfuric acid electrolyte
is absorbed by separators and plates and thus immobilized. Should the battery be accidentally
overcharged producing hydrogen and oxygen, special one-way valves allow the gases to
escape thus avoiding excessive pressure build-up. Otherwise, the battery is completely sealed
and is, therefore, maintenance-free, leak proof and usable in any position.
Battery Construction
Component

Positive plate

Negative plate

Container

Cover

Safety valve

Terminal

Separator

Electrolyte

Raw material

Lead dioxide



Lead

ABS

ABS

Rubber

Copper

Fiberglass

Sulfuric acid

Performance Characteristics

General Features














Absorbent Glass Mat (AGM) technology
for efficient gas recombination of up to
99% and freedom from electrolyte
maintenance or water adding.
Not restricted for air transport-complies
with IATA/ICAO Special Provision A67.
UL-recognized component.
Can be mounted in any orientation.
Computer designed lead, calcium tin alloy
grid for high power density.
Long service life, float or cyclic
applications.
Maintenance-free operation.
Low self discharge.

Dimensions and Weight
Length(mm / inch)
Width(mm / inch)
Height(mm / inch)
Total Height(mm / inch)
Approx. Weight(Kg / lbs)
* Weight deviation: ± 5%

181 / 7.13
77 / 3.03
167 / 6.57
167 / 6.57
5.9 / 13


Nominal Voltage
12V
Number of cell
6
Design Life
5 years
Nominal Capacity 77oF(25oC)
20 hour rate (1A, 10.5V)
20Ah
10 hour rate (1.85A, 10.5V)
18.5Ah
5 hour rate (3.45A, 10.5V)
17.25Ah
1 hour rate (13.4A, 9.6V)
13.4Ah
Internal Resistance
≤ 15mOhms
Fully Charged battery 77oF(25oC)
Self-Discharge
3% of capacity declined per month at 20oC(average)
Operating Temperature Range
Discharge
-20~60oC
Charge
-10~60oC
Storage
-20~60oC
o
o
300A(5s)

Max. Discharge Current 77 F(25 C)
Short Circuit Current

1000A

Charge Methods: Constant Voltage Charge
Cycle use
Maximum charging current
Temperature compensation
Standby use
Temperature compensation

77oF(25oC)
2.40-2.45VPC
8A
-30mV/oC
2.23-2.30VPC
-20mV/oC

Discharge Constant Current (Amperes at 77oF25oC)
End Point
Volts/Cell

5min

10min

15min

30min


1h

3h

5h

10h

20h

1.60V

75.0

51.2

39.6

22.4

13.4

5.36

3.72

1.93

1.07


1.65V

73.3

49.9

38.7

22.1

13.2

5.28

3.63

1.93

1.07

1.70V

71.5

48.7

37.8

21.7


13.0

5.20

3.54

1.90

1.04

1.75V

69.7

47.4

36.9

21.4

12.8

5.11

3.45

1.85

1.00


1.80V

67.9

46.1

36.0

21.0

12.5

5.03

3.36

1.76

0.95

3h

5h

Discharge Constant Power (Watts at 77oF25oC)
End Point
Volts/Cell

5min


10min

15min

30min

45min

1.60V

137

95

75.6

42.7

32.8

25.5 15.3 10.6 7.27

1.65V

132

93

74.3


42.1

32.4

25.2 15.2 10.5 7.18

1.70V

128

91

73.0

41.5

32.0

25.0 15.0 10.4 7.09

1.75V

123

89.4

71.8

40.9


31.6

24.7 14.8 10.3 7.00

1.80V

119

88.0

70.5

40.3

31.2

24.5 14.6 10.2 6.99

1h

2h

(Note)The above characteristics data are average values obtained within
three charge/discharge cycles not the mimimum values.
All data shall be changed without notice,Vision reserves the right to explain
and update the information contained hereinto.

page1 of 2


www.vision-batt.com


13.0

12V20Ah

Constant voltage charging
o
characteristic (0.25CA,25 C)

(%) (XCA) (V)
140

12.0

Voltage(v)

Voltage

O

Discharge characteristic (25 C)

Current

Charged
Volume

CP12200


120

0.25

100

0.20

11.0
10.0

80

9.0

60

0.15

20

0.05

2 3

5
min

10


20 30

60

5
h

2 3

10

0

0

20 30

Charge Voltage

12.0
11.0

0

0 1

Charged Volume

14.0

13.0

0.10

40

8.0

15.0

Charging Current

0

2

4

6

8

10

12

14

16


18

20

Charging time (hours)

Discharge time

Relationship between
charging voltage and temperature

Self-discharge characteristic
110
100

C y c le

15.0

Capacity(%)

Voltage(V)

15.6
Use

14.4
S ta n d

13.8


by Use

90
80
70
60

13.2

o

o

C

o

C

C

50

-10

0

10
20

30
40
Ambient temperature( oC)

50

40

60

0

2

4

6

8
10
12
14
Storage time: months

16

18

20


Cycle service life in relation to
depth of discharge

Life characteristics of Standby use
120

120
100
Capacity(%)

Capacity(%)

100

80

60

Testing conditions:floating voltage:2.27 to 2.30V Cell
ambient temperature: 25 oC(77 oF)

80
60

40

40

20


20

1

0

2
Life(year)

0

3

30% Depth of discharge

100% D.O.D. 50% D.O.D.

200

Temperature effects on float life

400
600
800
1000
Number of cycles(cycles)

1200

1400


Temperature effects on capacity

10

120

Capacity (%)

Life(years)

100

2.30V Cell
1

C
0 .0 5
0 .1 C
C
2
.
0

80
60

1 .0 C
2 .0 C


40

3 .0 C

20
0.1

10

20

30

40

50

0
-20

60

-10

0

10

20


30

40

Temperature( oC)

THE INTERNATIONAL CERTIFICATION NETWORK

ISO9001:2008

MH25860

G4M19906-9202-E-16

www.vision-batt.com

Shenzhen Center Power Tech. Co., Ltd.
Center Power Industrial Park, Tongfu Industrial District Dapeng Town, 518120 Shenzhen, China
Tel: (+86-755) 8431 8088 Fax: (+86-755) 8431 8038 E-mail:
Copy Right Shenzhen Center Power Technology Co., Ltd (Edition 2014-1)

Page 2 of 2

50( o C)



×