Tải bản đầy đủ (.pdf) (2 trang)

Catalogue cấu tạo chi tiết sử dụng ắc QUY UPS CP1272

Bạn đang xem bản rút gọn của tài liệu. Xem và tải ngay bản đầy đủ của tài liệu tại đây (435.63 KB, 2 trang )

CP1272

12V 7.2Ah(20hr)

The rechargeable batteries are lead-lead dioxide systems. The dilute sulfuric acid
electrolyte is absorbed by separators and plates and thus immobilized. Should the
battery be accidentally overcharged producing hydrogen and oxygen, special oneway valves allow the gases to escape thus avoiding excessive pressure build-up.
Otherwise, the battery is completely sealed and is, therefore, maintenance-free,
leak proof and usable in any position.
Battery Construction
Component

Positive plate

Negative plate

Container

Cover

Safety valve

Terminal

Separator

Electrolyte

Raw material

Lead dioxide



Lead

ABS

ABS

Rubber

Copper

Fiberglass

Sulfuric acid

Performance Characteristics

General Features














Absorbent Glass Mat (AGM) technology
for efficient gas recombination of up to
99% and freedom from electrolyte
maintenance or water adding.
Not restricted for air transport-complies
with IATA/ICAO Special Provision A67.
UL-recognized component.
Can be mounted in any orientation.
Computer designed lead, calcium tin alloy
grid for high power density.
Long service life, float or cyclic
applications.
Maintenance-free operation.
Low self discharge.

Dimensions and Weight
Length(mm / inch)
Width(mm / inch)
Height(mm / inch)
Total Height(mm / inch)
Approx. Weight(Kg / lbs)
* Weight deviation: ± 5%

151 / 5.94
65 / 2.56
94 / 3.70
100 / 3.94
2.5 / 5.51


Nominal Voltage
12V
Number of cell
6
Design Life
5 years
o
o
Nominal Capacity 77 F(25 C)
20 hour rate (0.36A, 10.5V)
7.2Ah
10 hour rate (0.69A, 10.5V)
6.9Ah
5 hour rate (1.16A, 10.5V)
5.8Ah
1 hour rate (4.8A, 9.6V)
4.8Ah
Internal Resistance
≤ 30mOhms
Fully Charged battery 77oF(25oC)
Self-Discharge
3% of capacity declined per month at 20oC(average)
Operating Temperature Range
Discharge
-20~60oC
Charge
-10~60oC
Storage
-20~60oC
o

o
105A(5s)
Max. Discharge Current 77 F(25 C)
Short Circuit Current

350A

Charge Methods: Constant Voltage Charge
Cycle use
Maximum charging current
Temperature compensation
Standby use
Temperature compensation

77oF(25oC)
2.40-2.45VPC
2.88A
-30mV/oC
2.23-2.30VPC
-20mV/oC

Discharge Constant Current (Amperes at 77oF25oC)
End Point
Volts/Cell
1.60V
1.65V
1.70V
1.75V
1.80V


5min 10min 15min 30min
30.0
28.4
26.8
25.2
23.5

18.8
17.9
17.0
16.0
15.1

15.3
14.6
13.9
13.2
12.5

8.50
8.15
7.86
7.56
7.18

1h

3h

5h


10h

20h

4.80
4.63
4.44
4.25
4.04

1.88
1.82
1.76
1.69
1.64

1.29
1.25
1.20
1.16
1.12

0.71
0.70
0.70
0.69
0.67

0.38

0.38
0.37
0.36
0.35

Discharge Constant Power (Watts at 77oF25oC)
End Point
Volts/Cell
1.60V
1.65V
1.70V
1.75V
1.80V

5min 10min 15min 30min 45min
53.3
50.7
48.1
45.6
43.1

35.8
34.0
32.2
30.4
28.6

28.1
27.0
25.9

24.8
23.8

15.5
14.9
14.3
13.7
13.2

11.8
11.3
10.8
10.4
10.0

1h

2h

3h

5h

9.30
8.90
8.53
8.28
7.90

5.13

5.02
4.89
4.73
4.58

3.68
3.59
3.49
3.38
3.27

2.38
2.34
2.30
2.25
2.19

(Note)The above characteristics data are average values obtained within
three charge/discharge cycles not the mimimum values.
All data shall be changed without notice,Vision reserves the right to explain
and update the information contained hereinto.

page1 of 2

www.vision-batt.com


13.0

Voltage


O

Discharge characteristic (25 C)

Current

Charged
Volume

CP1272

12V7.2Ah

Constant voltage charging
o
characteristic (0.25CA,25 C)

(%) (XCA) (V)
140

Voltage(v)

12.0
11.0

120

0.25


100

0.20

10.0

80
9.0

60

8.0

40

0

0 1

2 3

5

10
min

20 30

2 3


60

5

20
0

0

h

Charged Volume

14.0

Charge Voltage

13.0

0.10
0.05

20 30

10

0.15

15.0


12.0
11.0

Charging Current

0

2

4

6

Discharge time

(V/8V)

(V/6V)

(V/4V)

(V/CELL)

10.4

7.8

5.2

2.6


15.0

10.0

7.5

5.0

2.5

14.4

9.6

7.2

4.8

2.4

13.2

9.2
8.8

6.9
6.6

4.6

4.4

12

14

16

18

20

Self-discharge characteristic

100
90
CY

S TA

13.8

10

110

2.3

CL


EU

ND B

Capacity(%)

(V/12V)

Relationship between
charging voltage and temperature

15.6

8

Charging time (hours)

SE

Y US

80
70
60

o

E

o


C

o

C

C

50

2.2

40
-10

0

10
20
30
40
Ambient temperature( oC)

50

0

60


2

4

6

8

10

12

14

16

18

20

Storage time: months

Cycle service life in relation to
depth of discharge

Life characteristics of Standby use
120

120
100

Capacity(%)

Capacity(%)

100

80

60

Testing conditions: floating voltage: 2.27 to 2.30V Cell
ambient temperature: 25 oC(77 oF)

40

80
60

30% Depth of discharge

100% D.O.D. 50% D.O.D.

40
20

20

0

0


1

2
Life(year)

200

3

Temperature effects on float life

400
600
800
1000
Number of cycles(cycles)

1200

1400

Temperature effects on capacity

10

120

Capacity (%)


Life(years)

100

1

80
60
40
20

0.1
10

20

30

40

50

0
-20

60

-10

0


10

20

30

40

Temperature( oC)

THE INTERNATIONAL CERTIFICATION NETWORK

ISO9001:2008

MH25860

G4M19906-9202-E-16

www.vision-batt.com

Shenzhen Center Power Tech. Co., Ltd.
Center Power Industrial Park, Tongfu Industrial District Dapeng Town, 518120 Shenzhen, China
Tel: (+86-755) 8431 8088 Fax: (+86-755) 8431 8038 E-mail:
Copy Right Shenzhen Center Power Technology Co., Ltd (Edition 2014-1)

Page 2 of 2