Tải bản đầy đủ (.pdf) (2 trang)

Catalogue cấu tạo chi tiết sử dụng ắc QUY UPS CP1212

Bạn đang xem bản rút gọn của tài liệu. Xem và tải ngay bản đầy đủ của tài liệu tại đây (750.41 KB, 2 trang )

CP1212

Shenzhen Center Power
Tech.Co.Ltd,.

12V 1.2Ah(20hr)

Overview

The rechargeable batteries are lead-lead dioxide systems. The dilute sulfuric acid electrolyte is
absorbed by separators and plates and thus immobilized. Should the battery be accidentally
overcharged producing hydrogen and oxygen, special oneway valves allow the gases to escape
thus avoiding excessive pressure build-up. Otherwise, the battery is completely sealed and is,
therefore, maintenance-free, leak proof and usable in any position.

Battery Construction
Component

Positive plate

Negative plate

Raw material

Lead dioxide

Lead

Container Cover
ABS


General Features

Maintenance-free operation.
Low self discharge.
Case and cover available in both standard and flame
retardant ABS.

Dimensions and Weight

* Weight deviation: ± 5%

Terminal

Separator

Electrolyte

Rubber

Copper

Fiberglass

Sulfuric acid

Battery Specification

Absorbent Glass Mat (AGM) technology for efficient gas
recombination of up to 99% and freedom from
electrolyte maintenance or water adding.

Not restricted for air transport-complies with IATA/ICAO
Special Provision A67.
UL-recognized component.
Can be mounted in any orientation.
Computer designed lead, calcium tin alloy grid for high
power density.
Long service life, float or cyclic applications.

Length(mm / inch)
Width(mm / inch)
Height(mm / inch)
Total Height(mm / inch)
Approx. Weight(Kg / lbs)

Safety valve

ABS

97 / 3.82
43 / 1.69
52 / 2.05
58 / 2.28
0.53 / 1.17

Performance Characteristics
12V
Nominal Voltage
6
Number of cell
5 years

Design Life
Nominal Capacity 77℉(25℃)
20 hour rate (0.06A, 10.5V)
1.2Ah
10 hour rate (0.117A, 10.5V)
1.17Ah
5 hour rate (0.23A, 10.5V)
1.15Ah
1 hour rate (0.89A, 9.6V)
0.89Ah
Internal Resistance
Fully Charged battery 77℉(25℃)
≤55mOhms
Self-Discharge
3% of capacity declined per month at 20℃(average)
Operating Temperature Range
Discharge
-20~60℃
Charge
-10~60℃
Storage
-20~60℃
18.0A(5s)
Max. Discharge Current 77℉(25℃)
60A
Short Circuit Current
Charge Methods: Constant Voltage Charge 77℉(25℃)
Cycle use
2.30-2.35VPC
Maximum charging current

0.48A
Temperature compensation
-30mV/℃
Standby use
2.23-2.27VPC
Temperature compensation
-20mV/℃

Discharge Constant Current (Amperes at 77oF25oC)
End Point
Volts/Cell

5min

10min

15min

30min

1h

3h

1.60V

5.72

3.85


2.67

1.49

0.89

0.39

5h

10h

20h

0.25 0.129 0.065

1.65V

5.42

3.66

2.55

1.43

0.86

0.37


0.24 0.125 0.064

1.70V

5.12

3.48

2.43

1.36

0.83

0.36

0.24 0.120 0.064

1.75V

4.80

3.28

2.31

1.30

0.79


0.34

0.23 0.117 0.060

1.80V

4.48

3.08

2.18

1.23

0.76

0.33

0.22 0.115 0.060

Discharge Constant Power (Watts at 77oF25oC)
End Point
Volts/Cell
1.60V

5min 10min 15min

30min

45min


1h

9.90

6.24

2.94

1.79

0.73

0.50 0.257 0.130
0.49 0.253 0.127

5.14

2h

3h

5h

1.65V

9.28

5.87


4.85

2.78

1.72

0.72

1.70V

8.67

5.51

4.58

2.64

1.64

0.69

0.48 0.249 0.124

1.75V

8.06

5.15


4.29

2.49

1.56

0.67

0.47 0.245 0.121

1.80V

7.47

4.79

4.00

2.33

1.47

0.66

0.46 0.240 0.113

(Note)The above characteristics data are average values
obtained within three charge/discharge cycles not the mimimum
values.All data shall be changed without notice,Vision reserves
the right to explain and update the information contained hereinto.


Shenzhen Center Power Tech.Co.Ltd,.

STOCK CODE: 002733

www.vision-batt.com


13.0

Current

Charged
Volume

Discharge characteristic (25 OC)

Voltage

CP1212

Shenzhen Center Power
Tech.Co.Ltd,.

12V 1.2Ah(20hr)

Constant voltage charging
characteristic (0.25CA,25 ℃)

(%) (XCA) (V)

140

Voltage(v)

12.0
11.0
0.23A 0.117A 0.060A
0.36A

10.0
4A

9.0

120

0.25

100

0.20

80

2.67A1.49A 0.89A

0.15
0.10

40


0

0 1

2 3

5
min

10

20 30

60

5 0 1
h

2 3

20

0.05

0

0

30


Charged Volume

14.0

Charge Voltage

13.0

60

8.0

15.0

12.0
11.0
0

Charging Current
2

4

Discharge time

8

10


12

14

16

18

20

Charging time (hours)

Relationship between
charging voltage and temperature

Self-discharge characteristic

100

15.6
Capacity(%)

Cycle

15.0

Use

14.4
Stand


13.8

byUs e

90
80
70
60

13.2

-10

6

50
40
30
20
10
Ambient temperature(℃)

0

40

60

50


0

2

4

6

8
10
12
14
Storage time: months

16

18

20

Cycle service life in relation to
depth of discharge

Life characteristics of Standby use
120

120
100
Capacity(%)


80

60

Testing conditions:floating voltage:2.27 to 2.30V Cell
ambient temperature: 25oC(77oF)

80
60

40

40

20

20

1

0

2
Life(year)

30% Depth of discharge

100% D.O.D. 50% D.O.D.


0

3

200

Temperature effects on float life

400
600
800
1000
Number of cycles(cycles)

1200

1400

Temperature effects on capacit

10

120
100

2.30V Cell
1

Capacity (%)


Capacity(%)

100

C
0.05
0.1C
C
02.

80
60

1.0C
2.0C

40

3.0C

20
0.1

10

20

30

40


50

60

Temperature ( ℃)

Shenzhen Center Power Tech.Co.Ltd,.

-20

-10

0

10

20

30

40

50

Temperature ( ℃)

STOCK CODE: 002733

www.vision-batt.com




×