CP677

6V 7.7Ah(20hr)

The rechargeable batteries are lead-lead dioxide systems. The dilute sulfuric acid
electrolyte is absorbed by separators and plates and thus immobilized. Should the
battery be accidentally overcharged producing hydrogen and oxygen, special oneway valves allow the gases to escape thus avoiding excessive pressure build-up.
Otherwise, the battery is completely sealed and is, therefore, maintenance-free,
leak proof and usable in any position.
Battery Construction
Component

Positive plate

Negative plate

Container

Cover

Safety valve

Terminal

Separator

Electrolyte

Raw material

Lead dioxide



Lead

ABS

ABS

Rubber

Copper

Fiberglass

Sulfuric acid

Performance Characteristics

General Features














Absorbent Glass Mat (AGM) technology
for efficient gas recombination of up to
99% and freedom from electrolyte
maintenance or water adding.
Not restricted for air transport-complies
with IATA/ICAO Special Provision A67.
UL-recognized component.
Can be mounted in any orientation.
Computer designed lead, calcium tin alloy
grid for high power density.
Long service life, float or cyclic
applications.
Maintenance-free operation.
Low self discharge.

Dimensions and Weight
Length(mm / inch)
Width(mm / inch)
Height(mm / inch)
Total Height(mm / inch)
Approx. Weight(Kg / lbs)
* Weight deviation: ± 5%

151 / 5.94
34 / 1.34
94 / 3.70
97 / 3.82
1.34 / 2.95


Nominal Voltage
6V
Number of cell
3
Design Life
5 years
o
o
Nominal Capacity 77 F(25 C)
20 hour rate (0.385A, 5.25V)
7.7Ah
10 hour rate (0.72A, 5.25V)
7.2Ah
5 hour rate (1.25A, 5.25V)
6.25Ah
1 hour rate (5.12A, 4.8V)
5.12Ah
Internal Resistance
≤ 13mOhms
Fully Charged battery 77oF(25oC)
Self-Discharge
3% of capacity declined per month at 20oC(average)
Operating Temperature Range
Discharge
-20~60oC
Charge
-10~60oC
Storage
-20~60oC
o

o
115.5A(5s)
Max. Discharge Current 77 F(25 C)
Short Circuit Current

385A

Charge Methods: Constant Voltage Charge
Cycle use
Maximum charging current
Temperature compensation
Standby use
Temperature compensation

77oF(25oC)
2.40-2.45VPC
3.08A
-15mV/oC
2.23-2.30VPC
-10mV/oC

Discharge Constant Current (Amperes at 77oF25oC)
End Point
Volts/Cell
1.60V
1.65V
1.70V
1.75V
1.80V


5min 10min 15min 30min
30.6
28.8
27.8
25.8
23.1

18.9
18.3
17.9
17.3
16.8

15.3
14.9
14.6
14.3
13.4

8.77
8.56
8.39
8.12
7.63

1h

3h

5h


10h

20h

5.12
5.07
4.98
4.86
4.69

1.98
1.95
1.91
1.85
1.79

1.30
1.29
1.27
1.25
1.24

0.73
0.73
0.73
0.72
0.72

0.390

0.390
0.385
0.385
0.385

Discharge Constant Power (Watts at 77oF25oC)
End Point
Volts/Cell
1.60V
1.65V
1.70V
1.75V
1.80V

5min 10min 15min 30min 45min
58.1
56.2
54.5
50.7
44.7

37.1
36.3
35.4
34.2
33.0

30.4
29.9
29.1

28.3
26.7

17.4
17.0
16.7
16.1
15.3

13.1
13.0
12.8
12.4
12.0

1h

2h

3h

5h

10.20
10.10
9.94
9.66
9.32

5.50

5.45
5.40
5.34
5.26

3.96
3.92
3.85
3.72
3.58

2.48
2.45
2.42
2.39
2.33

(Note)The above characteristics data are average values obtained within
three charge/discharge cycles not the mimimum values.
All data shall be changed without notice,Vision reserves the right to explain
and update the information contained hereinto.

page1 of 2

www.vision-batt.com


6.5

6V7.7Ah


Constant voltage charging
o
characteristic (0.25CA,25 C)

(%) (XCA) (V)
140

6.0
Voltage(v)

Voltage

O

Discharge characteristic (25 C)

Current

Charged
Volume

CP677

5.5

120

0.25


100

0.20

5.0
80
4.5

0.15
0.10

40

0
0 1

3

2

5

20 30

10

60

5


2 3

min

10

20 30

20

0.05

0

0

h

Charged Volume

7.0

Charge Voltage

6.5

60

4.0


7.5

6.0
5.5

Charging Current

0

2

4

6

Discharge time

8

10

12

14

16

18

20


Charging time (hours)

Relationship between
charging voltage and temperature

Self-discharge characteristic
110
100

Cycl

7.5

e Us

Capacity(%)

Voltage(V)

7.8

e

7.2
S ta n d

6.9

by Use


90
80
70
60

6.6

o

o

C

o

C

C

50

-10

0

10
20
30
40

Ambient temperature( oC)

50

40

60

0

2

4

6

8
10
12
14
Storage time: months

16

18

20

Cycle service life in relation to
depth of discharge


Life characteristics of Standby use
120

120
100
Capacity(%)

Capacity(%)

100

80

60

Testing conditions:floating voltage:2.27 to 2.30V Cell
ambient temperature: 25 oC(77 oF)

80
60

40

40

20

20


1

0

2
Life(year)

0

3

30% Depth of discharge

100% D.O.D. 50% D.O.D.

200

Temperature effects on float life

400
600
800
1000
Number of cycles(cycles)

1200

1400

Temperature effects on capacity


10

120

Capacity (%)

Life(years)

100

2.30V Cell
1

C
0 .0 5
0 .1 C
C
2
.
0

80
60

1 .0 C
2 .0 C

40


3 .0 C

20
0.1

10

20

30

40

50

0
-20

60

-10

0

10

20

30


40

Temperature( oC)

THE INTERNATIONAL CERTIFICATION NETWORK

ISO9001:2008

MH25860

G4M19906-9202-E-16

www.vision-batt.com

Shenzhen Center Power Tech. Co., Ltd.
Center Power Industrial Park, Tongfu Industrial District Dapeng Town, 518120 Shenzhen, China
Tel: (+86-755) 8431 8088 Fax: (+86-755) 8431 8038 E-mail:
Copy Right Shenzhen Center Power Technology Co., Ltd (Edition 2014-1)

Page 2 of 2

50( o C)



×