NOTICE OF DISCLAIMER AND 
LIMITATION OF LIABILITY 
 SP-3-4426-AD10-B 
 To be published as ANSI/TIA/EIA-568-B.2-10 
 
 1 
NOTICE OF DISCLAIMER AND LIMITATION OF LIABILITY 2 
 3 
 4 
The document to which this Notice is affixed (the “Document”) has been prepared by one or more 5 
Engineering Committees or Formulating Groups of the Telecommunications Industry Association 6 
(“TIA”). TIA is not the author of the Document contents, but publishes and claims copyright to the 7 
Document pursuant to licenses and permission granted by the authors of the contents. 8 
TIA Engineering Committees and Formulating Groups are expected to conduct their affairs in 9 
accordance with the TIA Engineering Manual (“Manual”), the current and predecessor versions of 10 
which are available at  TIA’s 11 
function is to administer the process, but not the content, of document preparation in accordance 12 
with the Manual and, when appropriate, the policies and procedures of the American National 13 
Standards Institute (“ANSI”). TIA does not evaluate, test, verify or investigate the information, 14 
accuracy, soundness, or credibility of the contents of the Document. In publishing the Document, 15 
TIA disclaims any undertaking to perform any duty owed to or for anyone. 16 
If the Document is identified or marked as a project number (PN) document, or as a standards 17 
proposal (SP) document, persons or parties reading or in any way interested in the Document are 18 
cautioned that: (a) the Document is a proposal; (b) there is no assurance that the Document will be 19 
approved by any Committee of TIA or any other body in its present or any other form; (c) the 20 
Document may be amended, modified or changed in the standards development or any editing 21 
process. 22 
The use or practice of contents of this Document may involve the use of intellectual property rights 23 
(“IPR”), including pending or issued patents, or copyrights, owned by one or more parties. TIA 24 
makes no search or investigation for IPR. When IPR consisting of patents and published pending 25 
patent applications are claimed and called to TIA’s attention, a statement from the holder thereof is 26 
requested, all in accordance with the Manual. TIA takes no position with reference to, and disclaims 27 
any obligation to investigate or inquire into, the scope or validity of any claims of IPR. TIA will 28 
neither be a party to discussions of any licensing terms or conditions, which are instead left to the 29 
parties involved, nor will TIA opine or judge whether proposed licensing terms or conditions are 30 
reasonable or non-discriminatory. TIA does not warrant or represent that procedures or practices 31 
suggested or provided in the Manual have been complied with as respects the Document or its 32 
contents. 33 
TIA does not enforce or monitor compliance with the contents of the Document. TIA does not 34 
certify, inspect, test or otherwise investigate products, designs or services or any claims of 35 
compliance with the contents of the Document. 36 
ALL WARRANTIES, EXPRESS OR IMPLIED, ARE DISCLAIMED, INCLUDING WITHOUT 37 
LIMITATION, ANY AND ALL WARRANTIES CONCERNING THE ACCURACY OF THE 38 
CONTENTS, ITS FITNESS OR APPROPRIATENESS FOR A PARTICULAR PURPOSE OR 39 
USE, ITS MERCHANTABILITY AND ITS NON-INFRINGEMENT OF ANY THIRD PARTY’S 40 
INTELLECTUAL PROPERTY RIGHTS. TIA EXPRESSLY DISCLAIMS ANY AND ALL 41 
RESPONSIBILITIES FOR THE ACCURACY OF THE CONTENTS AND MAKES NO 42 
REPRESENTATIONS OR WARRANTIES REGARDING THE CONTENT’S COMPLIANCE WITH 43 
ANY APPLICABLE STATUTE, RULE OR REGULATION, OR THE SAFETY OR HEALTH 44 
EFFECTS OF THE CONTENTS OR ANY PRODUCT OR SERVICE REFERRED TO IN THE 45 
DOCUMENT OR PRODUCED OR RENDERED TO COMPLY WITH THE CONTENTS. 46 
 47 
SP-3-4426-AD10-B 
To be published as ANSI/TIA/EIA-568-B.2-10 
TIA SHALL NOT BE LIABLE FOR ANY AND ALL DAMAGES, DIRECT OR INDIRECT, ARISING FROM 1 
OR RELATING TO ANY USE OF THE CONTENTS CONTAINED HEREIN, INCLUDING WITHOUT 2 
LIMITATION ANY AND ALL INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES 3 
(INCLUDING DAMAGES FOR LOSS OF BUSINESS, LOSS OF PROFITS, LITIGATION, OR THE LIKE), 4 
WHETHER BASED UPON BREACH OF CONTRACT, BREACH OF WARRANTY, TORT (INCLUDING 5 
NEGLIGENCE), PRODUCT LIABILITY OR OTHERWISE, EVEN IF ADVISED OF THE POSSIBILITY 6 
OF SUCH DAMAGES. THE FOREGOING NEGATION OF DAMAGES IS A FUNDAMENTAL 7 
ELEMENT OF THE USE OF THE CONTENTS HEREOF, AND THESE CONTENTS WOULD NOT BE 8 
PUBLISHED BY TIA WITHOUT SUCH LIMITATIONS 9 
 10 
NOTICE 11 
 12 
{TIA staff to insert applicable text here.} 13 
SP-3-4426-AD10-B, draft 4.0 (to be published as ANSI/TIA/EIA-568-B.2-10) 04/06/06  
i 
TRANSMISSION PERFORMANCE SPECIFICATIONS 1 
FOR 2 
4-PAIR 100 Ω AUGMENTED CATEGORY 6 CABLING 3 
 4 
TABLE OF CONTENTS 5 
 6 
1
 INTRODUCTION 1 7 
2 PURPOSE AND SCOPE 1 8 
3 NORMATIVE REFERENCES 2 9 
4 DEFINITIONS, ACRONYMS & ABBREVIATIONS 2 10 
4.1
 Definitions 2 11 
4.2
 Acronyms and abbreviations 3 12 
5
 TEST CONFIGURATIONS 4 13 
6 CABLING AND COMPONENTS 5 14 
6.1
 Recognized cable 5 15 
6.2
 Recognized connecting hardware 5 16 
6.3
 Cords 5 17 
7
 TRANSMISSION REQUIREMENTS 6 18 
7.1
 Insertion loss 6 19 
7.1.1
 Cable insertion loss 6 20 
7.1.2 Connecting hardware insertion loss 7 21 
7.1.3 Cabling insertion loss 8 22 
7.1.3.1 Channel insertion loss 8 23 
7.1.3.2 Permanent link insertion loss 9 24 
7.2 
 NEXT loss and PSNEXT loss 10 25 
7.2.1
 NEXT loss 10 26 
7.2.1.1 Cable NEXT loss 10 27 
7.2.1.2 Connecting hardware NEXT loss 11 28 
7.2.1.3 Work area, equipment, and patch cord NEXT loss 12 29 
7.2.1.4 Channel NEXT loss 14 30 
7.2.1.5 Permanent link NEXT loss 15 31 
7.2.2 PSNEXT loss 16 32 
7.2.2.1 Cable PSNEXT loss 16 33 
7.2.2.2
 Channel PSNEXT loss 17 34 
7.2.2.3
 Permanent link PSNEXT loss 18 35 
7.3
 ELFEXT, FEXT loss, and PSELFEXT 19 36 
7.3.1
 ELFEXT 19 37 
7.3.1.1 Cable ELFEXT 19 38 
7.3.1.2 Channel ELFEXT 20 39 
7.3.1.3
 Permanent link ELFEXT 21 40 
7.3.2
 FEXT loss 22 41 
7.3.2.1 Connecting hardware FEXT loss 22 42 
7.3.3
 PSELFEXT 23 43 
7.3.3.1 Cable PSELFEXT 23 44 
7.3.3.2
 Channel PSELFEXT 24 45 
7.3.3.3
 Permanent link PSELFEXT 25 46 
7.4
 Return loss 26 47 
7.4.1
 Horizontal cable return loss 26 48 
7.4.2
 Cord cable return loss 27 49 
04/06/06 SP-3-4426-AD10-B, draft 4.0 (to be published as ANSI/TIA/EIA-568-B.2-10) 
ii 
7.4.3
 Connecting hardware return loss 28 1 
7.4.4 
 Work area, equipment, and patch cord return loss 29 2 
7.4.5
 Cabling return loss 30 3 
7.4.5.1 Channel return loss 30 4 
7.4.5.2 Permanent link return loss 31 5 
7.5
 Propagation delay/delay skew 32 6 
7.5.1
 Cable propagation delay 32 7 
7.5.2
 Cabling propagation delay 33 8 
7.5.3
 Cable propagation delay skew 33 9 
7.5.4 Cabling propagation delay skew 33 10 
7.6
 Balance 33 11 
7.6.1
 Transverse conversion loss (TCL) 33 12 
7.6.1.1 Cable TCL 34 13 
7.6.1.2 Connecting hardware TCL 35 14 
7.6.1.3 Channel TCL 36 15 
7.6.2 ELTCTL and TCTL 37 16 
7.6.2.1 Cable ELTCTL 37 17 
7.6.2.2 Connecting hardware TCTL 38 18 
7.6.2.3 Channel ELTCTL 39 19 
7.7 DC resistance unbalance (TBD) 39 20 
7.7.1
 Cable DC resistance unbalance 39 21 
7.7.2 Connecting hardware DC resistance unbalance 39 22 
7.7.3 Channel DC resistance unbalance 39 23 
7.8
 ANEXT loss and PSANEXT loss 40 24 
7.8.1
 Cable PSANEXT loss 40 25 
7.8.2 Connecting hardware PSANEXT loss 41 26 
7.8.3 Channel PSANEXT loss 42 27 
7.8.4 Permanent link PSANEXT loss 43 28 
7.9
 Average ANEXT loss and PSANEXT loss 44 29 
7.9.1
 Average channel PSANEXT loss 44 30 
7.10
 AFEXT loss, AELFEXT, and PSAACRF 45 31 
7.10.1
 Cable PSAACRF 46 32 
7.10.2 Connecting hardware PSAFEXT loss 47 33 
7.10.3 Channel PSAACRF 48 34 
7.10.4
 Permanent link PSAACRF 49 35 
7.11
 Average AELFEXT and PSAACRF 50 36 
7.11.1
 Average channel PSAACRF 50 37 
Annex A Cabling measurement requirements (normative) 51 38 
A.1
 General 51 39 
A.2
 Test setup and apparatus required 51 40 
Annex B Cable ANEXT loss and AFEXT loss reference test procedure (normative) 53
 41 
B.1
 Purpose 53 42 
B.2
 Equipment 53 43 
B.3
 Procedure 53 44 
B.4
 Results 53 45 
Annex C Connecting hardware ANEXT loss and AFEXT loss reference test procedure 46 
(normative) 54
 47 
C.1
 Purpose 54 48 
SP-3-4426-AD10-B, draft 4.0 (to be published as ANSI/TIA/EIA-568-B.2-10) 04/06/06  
iii 
C.2
 Measurement outline 54 1 
C.3
 Network analyzer and test fixture settings 54 2 
C.4
 Measurement floor 54 3 
C.5
 DUT setup for ANEXT loss and AFEXT loss measurement 54 4 
C.6
 Region of influence 57 5 
C.7
 PSANEXT loss and PSAFEXT loss calculation 57 6 
Annex D Channel ANEXT loss and AFEXT loss laboratory measurement procedures (normative)7 
 58
 8 
D.1
 General 58 9 
D.2
 Termination of pairs 58 10 
D.3
 Channel construction 58 11 
D.4
 Determining number of disturbing components 59 12 
D.5
 Channel ANEXT loss and AFEXT loss measurements and computations 60 13 
Annex E Field measurement method for alien crosstalk (normative) 61
 14 
E.1
 General 61 15 
E.2
 Frequency range 61 16 
E.3
 Test parameters 61 17 
E.4
 Test configurations 61 18 
E.5
 Processing measurement data 61 19 
E.5.1
 Significance condition testing 61 20 
E.5.2 Computing the PS ANEXT loss and PS AACR-F 61 21 
E.5.3 Applying the correction for the measurement floor (optional) 63 22 
E.6
 Power sum alien crosstalk test strategy 64 23 
E.6.1
 General guidelines for power sum alien crosstalk testing 64 24 
Annex F Modular plug cord test procedure (normative) 65 25 
F.1
 General 65 26 
F.2
 Network analyzer test configuration 65 27 
F.3
 Augmented category 6 modular plug cord test procedure 66 28 
F.4
 Augmented category 6 modular plug cord test head requirements 66 29 
F.4.1
 Augmented category 6 modular cord test head NEXT loss 66 30 
F.4.2 Augmented category 6 modular cord test head FEXT loss 67 31 
F.4.3
 Augmented category 6 modular cord test head return loss 67 32 
Annex G Connecting hardware test procedures (normative) 68
 33 
G.1
 General 68 34 
G.2
 Test setup and apparatus 68 35 
G.2.1
 Test balun characteristics 68 36 
G.2.2
 Impedance matching terminations 68 37 
G.2.2.1 Test fixture common mode impedance match 68 38 
G.2.2.2 Balun terminations 68 39 
G.2.2.3
 Resistor terminations 68 40 
G.2.2.4
 Termination performance at test interface 69 41 
G.3
 Modular outlet test considerations 69 42 
04/06/06 SP-3-4426-AD10-B, draft 4.0 (to be published as ANSI/TIA/EIA-568-B.2-10) 
iv 
G.3.1
 Test plug construction 69 1 
G.3.2
 Test plug qualification 69 2 
G.3.2.1
 Test plug qualification procedure 69 3 
G.3.3 Connecting hardware NEXT loss testing 70 4 
G.3.4 Procedure for terminating a test plug to direct measurement test head 70 5 
G.3.5 Augmented category 6 modular test plug NEXT loss requirements 71 6 
G.3.6 Augmented category 6 NEXT loss measurement reproducibility between labs 73 7 
G.4
 Augmented category 6 test plug FEXT loss 74 8 
G.4.1
 Augmented category 6 FEXT loss measurement reproducibility between labs 74 9 
G.5
 Test plug return loss testing 75 10 
G.5.1
 Return loss test lead considerations 75 11 
G.5.2 Test plug return loss requirements 75 12 
G.5.3 Test plug return loss measurement procedure 75 13 
G.5.4 Return loss lab-to-lab measurement accuracy 75 14 
Annex H Impedance controlled measurement fixture (normative) 76 15 
H.1
 General 76 16 
H.2
 Additional components for connection to a network analyzer 77 17 
H.3
 Test fixture calibration procedure 77 18 
H.3.1
 Open short and load calibration 77 19 
H.3.2 Through calibration 78 20 
H.4
 Test lead return loss measurement using pyramid impedance management fixture 78 21 
H.5
 Direct measurement fixture detailed construction 79 22 
H.6
 Test plug delay and port extension 81 23 
H.7
 Calibration and reference plane location 81 24 
H.8
 Network analyzer settings 81 25 
H.9
 Measurements 82 26 
H.10
 Alternative port extension procedure 83 27 
Annex I Accuracy requirements for level IIIe field testers (normative) 84
 28 
I.1
 General 84 29 
I.2
 Measurement performance requirements 84 30 
I.3
 Optional comparison method using the full frequency responses 86 31 
Annex J Augmented category 6 ScTP related specifications (normative) 88
 32 
J.1
 General 88 33 
J.2
 Insertion loss 88 34 
J.2.1
 Cable insertion loss 88 35 
J.3
 PSANEXT loss 89 36 
J.4
 Insertion loss de-rating length adjustment 89 37 
Annex K Modeling configurations (informative) 90
 38 
K.1
 General 90 39 
40 
SP-3-4426-AD10-B, draft 4.0 (to be published as ANSI/TIA/EIA-568-B.2-10) 04/06/06  
v 
LIST OF FIGURES 1 
Figure 1 - Supplemental schematic representation of a channel test configuration 4
 2 
Figure 2 - Supplemental schematic representation of a permanent link test configuration 5 3 
Figure A.1 - Measurement configurations for test balun qualification 52 4 
Figure B.1 - 6-around-1 cable test configuration 53 5 
Figure C.1 - Connecting hardware ANEXT loss measurement setup 55 6 
Figure D.1 - Example of a “6-around-1” cable arrangement in a channel 59 7 
Figure D.2 - Connector arrangement from an 8-port panel, in which 5 of the connectors are 8 
significant disturbers 59
 9 
Figure F.1 - Network analyzer configuration 65 10 
Figure G.1 - Test plug/direct measurement fixture with impedance controlled test fixture 70 11 
Figure H.1 - Test head assembly THI3KIT with baluns attached 76 12 
Figure H.2 - Test head assembly showing foil tape applied to baluns and shielding (optional) 13 
between baluns 77
 14 
Figure H.3 - Load calibration adapter arrangement 77 15 
Figure H.4 - Through calibration 78
 16 
Figure H.5 - Test setup for measurement of test lead return loss 78
 17 
Figure H.6 - Plug direct measurement fixture, view 1 79 18 
Figure H.7 - Plug direct measurement fixture, view 2 79 19 
Figure H.8 - Exploded assembly of the coaxial termination reference test head 80
 20 
Figure H.9 - Detailed view of the coaxial termination reference test head interface 81
 21 
Figure H.10 - Example of coaxial test head shorting plug 83 22 
Figure I.1 – Example of observed Level IIIe accuracy 87 23 
 24 
LIST OF TABLES 25 
 26 
Table 1 - Matrix of backward compatible mated component performance 1
 27 
Table 2 - Augmented category 6 cable insertion loss 6 28 
Table 3 – Augmented category 6 connecting hardware insertion loss 7 29 
Table 4 – Augmented category 6 channel insertion loss 8 30 
Table 5 – Augmented category 6 permanent link insertion loss 9 31 
Table 6 - Augmented category 6 cable NEXT loss 10 32 
Table 7 – Augmented category 6 connecting hardware NEXT loss 11 33 
Table 8 – Augmented category 6 connecting hardware NEXT loss 11 34 
Table 9 - Example augmented category 6 work area, equipment, and patch cord NEXT loss limits35 
 13
 36 
Table 10 – Augmented category 6 channel NEXT loss 14 37 
Table 11 – Augmented category 6 channel NEXT loss 14
 38 
Table 12 – Augmented category 6 permanent link NEXT loss 15
 39 
Table 13 – Augmented category 6 permanent link pair-to pair NEXT loss 15 40 
Table 14 - Augmented category 6 cable PSNEXT loss 16
 41 
Table 15 – Augmented category 6 channel PSNEXT loss 17 42 
Table 16 – Augmented category 6 channel PSNEXT loss 17 43 
Table 17 – Augmented category 6 permanent link PSNEXT loss 18
 44 
Table 18 – Augmented category 6 permanent link PSNEXT loss 18
 45 
Table 19 – Augmented category 6 cable ELFEXT 19 46 
Table 20 – Augmented category 6 channel ELFEXT 20
 47 
Table 21 – Augmented category 6 permanent link ELFEXT 21 48 
Table 22 – Augmented category 6 connecting hardware FEXT loss 22
 49 
Table 23 - Augmented category 6 cable PSELFEXT 23 50 
Table 24 – Augmented category 6 channel PSELFEXT 24
 51 
Table 25 – Augmented category 6 permanent link PSELFEXT 25
 52 
Table 26 - Augmented category 6 horizontal cable return loss 26
 53 
Table 27 - Augmented category 6 horizontal cable return loss 26 54 
04/06/06 SP-3-4426-AD10-B, draft 4.0 (to be published as ANSI/TIA/EIA-568-B.2-10) 
vi 
Table 28 - Augmented category 6 cord cable return loss 27
 1 
Table 29 - Augmented category 6 cord cable return loss 27
 2 
Table 30 - Augmented category 6 connecting hardware return loss 28
 3 
Table 31 - Augmented category 6 work area, equipment, and patch cord return loss 29 4 
Table 32 - Augmented category 6 work area, equipment, and patch cord return loss 29 5 
Table 33 – Augmented category 6 channel return loss 30 6 
Table 34 – Augmented category 6 channel return loss 30 7 
Table 35 – Augmented category 6 permanent link return loss 31
 8 
Table 36 – Augmented category 6 permanent link return loss 31
 9 
Table 37 - Augmented category 6 cable propagation delay 32 10 
Table 38 – Augmented category 6 cable TCL 34 11 
Table 39 – Augmented category 6 connecting hardware TCL 35 12 
Table 40 – Augmented category 6 channel TCL 36 13 
Table 41 – Augmented category 6 channel TCL 36 14 
Table 42 – Augmented category 6 cable ELTCTL 37 15 
Table 43 – Augmented category 6 connecting hardware TCTL 38 16 
Table 44 – Augmented category 6 channel ELTCTL 39 17 
Table 45 – Augmented category 6 cable PSANEXT loss 40 18 
Table 46 – Augmented category 6 connecting hardware PSANEXT loss 41 19 
Table 47 – Augmented category 6 channel PSANEXT loss 42 20 
Table 48 – Augmented category 6 channel PSANEXT loss 42 21 
Table 49 – Augmented category 6 permanent link PSANEXT loss 43 22 
Table 50 – Augmented category 6 permanent link PSANEXT loss 43 23 
Table 51 – Augmented category 6 channel average PSANEXT loss 44 24 
Table 52 – Augmented category 6 channel average PSANEXT loss 44 25 
Table 53 – Augmented category 6 cable PSAACRF loss 46 26 
Table 54 – Augmented category 6 connecting hardware PSAFEXT loss 47 27 
Table 55 – Augmented category 6 channel PSAACRF 48 28 
Table 56 – Augmented category 6 permanent link PSAACRF 49 29 
Table 57 – Augmented category 6 channel average PSAACRF 50 30 
Table A.1 - Test balun performance characteristics 51 31 
Table F.1 - Augmented category 6 modular cord test head return loss 67 32 
Table G.1 – Augmented category 6 connecting hardware NEXT loss for high and low plugs 45-3633 
 70
 34 
Table G.2 – Augmented category 6 direct measurement test plug NEXT loss limits 71 35 
Table G.3 – Augmented category 6 direct measurement test plug NEXT loss range 72 36 
Table G.4 – Augmented category 6 FEXT loss ranges for category 6 NEXT loss test plugs 73 37 
Table G.5 – Test plug NEXT loss measurement reproducibility between laboratories 73
 38 
Table G.6 – Augmented category 6 test plug FEXT loss ranges 74 39 
Table G.7 – Test plug FEXT loss measurement reproducibility between laboratories 74
 40 
Table H.1 - Direct measurement fixture residual NEXT loss and return loss 80
 41 
Table I.1 – Level IIIe field tester accuracy performance 84 42 
Table I.2 - Explanation of notes in table I.1 85
 43 
Table J.1 – Augmented category 6 ScTP cable insertion loss 88
 44 
Table J.2 – Augmented category 6 ScTP channel PSANEXT loss 89 45 
Table J.3 – Augmented category 6 ScTP channel PSANEXT loss 89
 46 
47 
SP-3-4426-AD10-B, draft 4.0 (to be published as ANSI/TIA/EIA-568-B.2-10) 04/06/06  
vii 
 1 
 2 
 3 
 4 
FOREWORD 5 
 6 
 7 
 8 
(This foreword is not part of the Standard) 9 
 10 
 11 
In 2003, the Telecommunications Industry Association (TIA) developed objectives for augmented 12 
category 6 cabling intended to support 10 Gigabit applications over a distance of 100 meters. At 13 
the request of the Institute of Electrical and Electronics Engineers (IEEE) 802.3 Committee, TIA 14 
agreed to specify augmented category 6 cabling systems and components to 500 MHz in order to 15 
support 10GBASE-T. The project was assigned to TR-42.7 under Engineering Committee TR-42. 16 
The TR-42.7 Sub-Committee cooperated with several groups related to this activity. 17 
 18 
TIA standards documents are developed within the Technical Committees of the TIA and the 19 
standards coordinating committees of the TIA standards board. Members of the committees 20 
serve voluntarily and without commission. The companies that they represent are not 21 
necessarily members of the TIA. The standards developed within the TIA represent a consensus 22 
of the broad expertise on the subject. This expertise comes from within the TIA as well as those 23 
outside of the TIA that have an expressed interest. The viewpoint expressed at the time that this 24 
standard was approved was from the contributors’ experience and the state of the art at that time. 25 
Users are encouraged to verify that they have the latest revision of the standard. 26 
 27 
This standard has been prepared by the TR-42.7 Subcommittee and approved by the 28 
Engineering Committee TR-42. 29 
 30 
There are 10 annexes in this Standard. Annexes A, B, C, D, E, F, G, H, I, and J, are normative 31 
and considered a mandatory part of this Standard. Annex K is informative and not considered a 32 
part of this Standard. 33 
34 
SP-3-4426-AD10-B, draft 4.0 (to be published as TIA/EIA-568-B.2-10) 04/06/06  
1 
1 INTRODUCTION 1 
This Standard specifies requirements and recommendations for 100 Ω 4-pair augmented 2 
category 6 cabling, cables, cords, and connecting hardware to support the operation of high-speed 3 
applications, such as IEEE 802.3 10GBASE-T, over up to100 meters of structured balanced 4 
twisted-pair copper cabling.
 In addition, augmented category 6 cabling, cables, cords, and 5 
connecting hardware shall meet or exceed all the requirements of ANSI/TIA/EIA-568-B.1, 6 
ANSI/TIA/EIA-568-B.2, and ANSI/TIA/EIA-568-B.2-1. Compliance with this Standard does not imply 7 
compatibility with cabling having nominal impedance values other than 100 Ω. 8 
 9 
The requirements in this Standard are for 100 Ω augmented category 6 balanced twisted-pair 10 
cabling systems and components. Augmented category 6 cabling provides higher performance 11 
than category 6 and recognizes advances in cabling technology. Augmented category 6 shall be 12 
backward compatible with categories 3, 5, 5e, and 6 as specified in ANSI/TIA/EIA-568-B.1, 13 
ANSI/TIA/EIA-568-B.2, and ANSI/TIA/EIA-568-B.2-1. Applications running on the lower category 14 
cabling shall be supported by augmented category 6. For augmented category 6, the 8-position 15 
modular jack interface shall be maintained at the telecommunications outlet connector in the work 16 
area. If different category components are to be mixed with augmented category 6 components, 17 
the combination shall meet the transmission requirements of the lower performing category. See 18 
table 1 for a matrix of mated component performance representative of backward compatibility. To 19 
ensure generic cabling system performance, component requirements are specified to support 20 
interoperability when products from different manufacturers are mated. 21 
Table 1 - Matrix of backward compatible mated component performance 22 
Category of Modular Connecting Hardware Performance  
Category 
3
1) 
Category 5 Category 5e Category 6 Augmented 
Category 6 
Category 3 
1)
 Category 3 Category 3 Category 3 Category 3 Category 3 
Category 5 Category 3 Category 5 Category 5 Category 5 Category 5 
Category 5e Category 3 Category 5 Category 5e Category 5e Category 5e 
Category 6 Category 3 Category 5 Category 5e Category 6 Category 6  
Augmented 
Category 6 
Category 3 Category 5 Category 5e Category 6 Augmented 
Category 6 
1) Category 3 plug performance requirements are assumed to be less restrictive than 
category 5e. 
 23 
Testing according to the procedures of this standard is intended to ensure backward compatibility 24 
with category 6. 25 
2 PURPOSE AND SCOPE 26 
To develop cabling and component specifications and test procedures to support the operation of 27 
high-speed applications, such as IEEE 802.3an 10GBASE-T, over up to100 meters of structured 28 
balanced twisted-pair copper cabling. This Standard specifies requirements and recommendations 29 
for 100 Ω 4-pair augmented category 6 cabling, cables, cords, and connecting hardware up to 30 
500 MHz. This Standard includes extending the frequency range and adding requirements 31 
(i.e. alien crosstalk) to those specified in ANSI/TIA/EIA-568-B.2 and its addenda. This cabling shall 32 
be known as augmented category 6. Augmented category 6 may be abbreviated as category 6A. 33 
34 
Modular Plug & 
Cord Performance 
04/06/06 SP-3-4426-AD10-B, draft 4.0 (to be published asTIA/EIA-568-B.2-10) 
2 
3 NORMATIVE REFERENCES 1 
The following standards contain requirements that, through reference in this text, constitute 2 
provisions of this Standard. At the time of publication, the editions indicated were valid. All 3 
standards are subject to revision; parties to agreements based on this Standard are encouraged to 4 
investigate the possibility of applying the most recent editions of the standards indicated. ANSI and 5 
TIA maintain registers of currently valid national standards published by them. 6 
ANSI/ICEA S-80-576, Communications Wire and Cable for Wiring Premises, 1994 7 
ANSI/ICEA S-90-661, Individually Unshielded Twisted Pair Indoor Cable for Use in Communication 8 
Wiring Systems, 1994 9 
ANSI/TIA/EIA-568-B.1, Commercial Building Telecommunications Standard Part 1: General 10 
Requirements, 2001 11 
ANSI/TIA/EIA-568-B.2, Commercial Building Telecommunications Standard Part 2: Balanced 12 
Twisted-pair Cabling Components, 2001 13 
ANSI/TIA/EIA-568-B.2-1, Commercial Building Telecommunications Standard Part 2: Addendum 1: 14 
Transmission Performance Specifications for 4-Pair 100 Ohm category 6 cabling, 2002 15 
ANSI/TIA/EIA-568-B.2-3, Additional Considerations for Insertion Loss and Return Loss Pass/Fail 16 
Determination, 2002 17 
ANSI/TIA/EIA-568-B.2-9, Additional Category 6 Balance Requirements and Measurement 18 
Procedures, pending publication 19 
ANSI/TIA/EIA-568-B.2-11, Specification for Increased Diameter of 4-Pair UTP and SCTP Cable 20 
2005 21 
ANSI/TIA/EIA-568-B.3, Commercial Building Telecommunications Standard Part 3: Optical Fiber 22 
Cabling Components, 2000 23 
ASTM D 4566-98, Standard Test Methods for Electrical Performance Properties of Insulations and 24 
Jackets for Telecommunications Wire and Cable, 1998 25 
IEC 60603-7, Connectors for frequencies below 3 MHz for use with printed boards – Part 7: Detail 26 
specification for connectors, 8-way, including fixed and free connectors with common mating 27 
features, with assessed quality, 1996 28 
4 DEFINITIONS, ACRONYMS & ABBREVIATIONS 29 
4.1 Definitions 30 
The generic definitions in this section have been formulated for use by the entire family of 31 
telecommunications infrastructure standards. As such, the definitions do not contain mandatory 32 
requirements of the Standard. Specific requirements are found in the normative sections of this 33 
Standard. 34 
NOTE - The definitions of equal level far end crosstalk (ELFEXT) and power sum equal 35 
level far end crosstalk (PSELFEXT) as used in this standard are defined in ASTM D 4566 36 
as attenuation to crosstalk ratio far end (ACR-F) and power sum attenuation to crosstalk 37 
ratio, far end (PSACR-F) respectively. 38 
alien crosstalk: Signal coupling from disturbing pairs into a disturbed pair of a neighboring channel 39 
or part thereof. 40 
alien far-end crosstalk loss: Signal coupling from near-end disturbing channel pairs into a 41 
disturbed pair of a neighboring channel or part thereof, measured at the far-end. 42 
alien near-end crosstalk loss: Signal coupling from near-end disturbing channel pairs into a 43 
disturbed pair of a neighboring channel or part thereof, measured at the near-end. 44 
average ANEXT loss: The average signal coupling from near-end disturbing channel pairs into a 45 
disturbed pair of a neighboring channel or part thereof, measured at the near-end. 46 
SP-3-4426-AD10-B, draft 4.0 (to be published as TIA/EIA-568-B.2-10) 04/06/06  
3 
average PSANEXT loss: The calculated average of the individual PSANEXT loss values for all 1 
four pairs in the disturbed channel 2 
cord cable: cable used to construct patch, work area, and equipment cords. 3 
power sum attenuation to alien crosstalk ratio far-end: A computation of signal coupling from 4 
multiple pairs of disturbing channels, to a disturbed pair in another channel, measured at the far-5 
end, and relative to the received signal level in the disturbed pair at the far-end. 6 
power sum alien far-end crosstalk loss: A computation of signal coupling from multiple near-end 7 
disturbing channel pairs into a disturbed pair of a neighboring channel or part thereof, measured at 8 
the far-end. 9 
power sum alien near-end crosstalk loss: A computation of signal coupling from multiple near-10 
end disturbing channel pairs into a disturbed pair of a neighboring channel or part thereof, 11 
measured at the near-end. 12 
power sum far-end crosstalk loss: A computation of the unwanted signal coupling from multiple 13 
transmitters at the near-end into a pair measured at the far-end. 14 
4.2 Acronyms and abbreviations 15 
AELFEXT Alien equal level far-end crosstalk 16 
AFEXT Alien far-end crosstalk 17 
ANEXT Alien near-end crosstalk 18 
CM Common mode 19 
DM Differential mode 20 
PSAACRF Power sum attenuation to alien crosstalk ratio far-end 21 
PSAFEXT Power sum alien far-end crosstalk 22 
PSANEXT Power sum alien near-end crosstalk 23 
PSFEXT Power sum far-end crosstalk 24 
25 
04/06/06 SP-3-4426-AD10-B, draft 4.0 (to be published asTIA/EIA-568-B.2-10) 
4 
5 TEST CONFIGURATIONS 1 
Cabling and component test configurations and procedures are specified in ANSI/TIA/EIA-568-B.1 2 
and ANSI/TIA/EIA-568-B.2 and their addenda with the additional requirements specified within this 3 
Standard. The channel test configuration is described in ANSI/TIA/EIA-568-B.1. A supplemental 4 
schematic representation of the channel test configuration is illustrated in figure 1. 5 
 6 
 7 
 8 
 9 
 10 
 11 
 12 
 13 
 14 
 15 
 16 
 17 
 18 
 19 
 20 
 21 
 22 
 23 
 24 
 25 
 26 
 27 
 28 
Figure 1 - Supplemental schematic representation of a channel test configuration 29 
30 
Legend  
Cables and cords Connecting hardware 
Work area cord A Telecommunications outlet/ 
Optional consolidation point cabling B connector WA 
Horizontal cabling C Optional consolidation 
Patch cord or jumper cable D point connector CP 
Telecommunications room Horizontal cross-connect or 
 equipment cord E interconnect C1, C2  
Maximum length 
 B + C 90 m (295 ft) 
 A + D + E 10 m (32.8 ft)  
Test 
equipment 
A
B
C
D
E 
Test 
equipment
CP WA 
C1 C2
Channel under test
SP-3-4426-AD10-B, draft 4.0 (to be published as TIA/EIA-568-B.2-10) 04/06/06  
5 
The permanent link test configuration is defined in ANSI/TIA/EIA-568-B.1. A supplemental 1 
schematic representation of the permanent link test configuration is illustrated in figure 2. 2 
 3 
 4 
 5 
 6 
 7 
 8 
 9 
 10 
 11 
 12 
 13 
 14 
 15 
 16 
 17 
 18 
 19 
 20 
 21 
 22 
 23 
Figure 2 - Supplemental schematic representation of a permanent link test configuration 24 
6 CABLING AND COMPONENTS 25 
The following category of twisted-pair cabling and components is recognized in addition to those 26 
identified in ANSI/TIA/EIA-568-B.2 and its addenda: 27 
 28 
 Augmented category 6: This designation applies to 100 Ω cabling and components whose 29 
transmission characteristics are specified up to 500 MHz. 30 
6.1 Recognized cable 31 
Augmented category 6 cable, of all types including horizontal, cord, backbone, and bundled and 32 
hybrid cables, shall conform to the respective cable types’ requirements given in clause 4 of 33 
ANSI/TIA/EIA-568-B.2 and its addenda and clause 7 of this Standard. 34 
 35 
Additional requirements for 100 Ω augmented category 6 ScTP cables are located in annex K of 36 
ANSI/TIA/EIA-568-B.2 and annex J of this Standard.
 37 
 38 
Bundling lower category cables with augmented category 6 cables may adversely affect alien 39 
crosstalk performance.
 40 
6.2 Recognized connecting hardware 41 
Augmented category 6 connecting hardware shall conform to the respective connecting hardware 42 
requirements given in clause 5 of ANSI/TIA/EIA-568-B.2 and its addenda and clause 7 of this 43 
Standard. 44 
6.3 Cords 45 
Augmented category 6 cords shall conform to the respective cord requirements given in clause 6 of 46 
ANSI/TIA-568-B.2 and its addenda and clause 7 of this Standard. 47 
48 
Legend  
Cables and cords Connecting hardware 
Test equipment cord F Telecommunications outlet/ 
Optional consolidation point cabling .B connector WA 
Horizontal cabling C Optional consolidation 
 point connector CP 
 Horizontal cross-connect or 
 interconnect C1 
Maximum length 
 B + C 90 m (295 ft)  
Test 
instrument 
F B
C
F 
Test 
instrument
CPWA 
C1 
Permanent link 
under test 
04/06/06 SP-3-4426-AD10-B, draft 4.0 (to be published asTIA/EIA-568-B.2-10) 
6 
7 TRANSMISSION REQUIREMENTS 1 
7.1 Insertion loss 2 
7.1.1 Cable insertion loss 3 
For all frequencies from 1 MHz to 500 MHz, augmented category 6 horizontal cable insertion loss 4 
shall meet the values determined using equation (1). Cable insertion loss shall be measured in 5 
accordance with clause C.1 of ANSI/TIA/EIA-568-B.2 at 20 ± 3°C or corrected to a temperature of 6 
20 °C using the correction factors specified in this clause. The values in table 2 are provided for 7 
information only. 8 
 9 
f
ffossInsertionL
mcable
2.0
01.08.1
100,
++≤
 dB (1) 10 
Augmented category 6 horizontal cable insertion loss shall also be verified at a temperature of 11 
40 ± 3 °C and 60 ± 3 °C and shall meet the requirements of equation (1) after adjusting for 12 
temperature. The maximum insertion loss for horizontal UTP cables shall be adjusted at elevated 13 
temperatures using a factor of 0.4 % increase per °C from 20 °C to 40 °C and 0.6% increase per °C 14 
for temperatures from 40 °C to 60 °C. The maximum insertion loss for horizontal ScTP cables shall 15 
be adjusted at elevated temperatures using a factor of 0.2% increase per °C from 20 °C to 60 °C. 16 
 17 
Table 2 - Augmented category 6 cable insertion loss 18 
 19 
Frequency 
(MHz) 
Insertion loss 
(dB) 
1.00 2.0 
4.00 3.7 
8.00 5.2 
10.00 5.9 
16.00 7.4 
20.00 8.3 
25.00 9.3 
31.25 10.4 
62.50 14.9 
100.00 19.0 
200.00 27.5 
250.00 31.0 
300.00 34.2 
400.00 40.0 
500.00 45.3 
 20 
 21 
 22 
For all frequencies from 1 MHz to 500 MHz, augmented category 6 UTP and ScTP cord cable 23 
insertion loss shall meet the values determined using equation (2),which has a de-rating factor of 24 
1.2. An insertion loss de-rating factor of 1.5 for cord cable is allowed with the appropriate guidance 25 
as described in annex . Cord cable insertion loss shall be measured at 20 ± 3° C or corrected to a 26 
temperature of 20 °C using a 0.4 %/°C correction factor for the measured insertion loss. 27  
28 
mcablemcablecord
ossInsertionLossInsertionL
100,100,_
2.1 ⋅≤ dB (2) 29 
 30 
 31 
32 
SP-3-4426-AD10-B, draft 4.0 (to be published as TIA/EIA-568-B.2-10) 04/06/06  
7 
7.1.2 Connecting hardware insertion loss 1 
For all frequencies from 1 MHz to 500 MHz, augmented category 6 connecting hardware insertion 2 
loss shall meet the values determined using equation (3). The values in table 3 are provided for 3 
information only. Calculations that result in insertion loss values less than 0.1 dB shall revert to a 4 
requirement of 0.1 dB maximum. 5 
 6 
fossInsertionL
conn
02.0≤ dB (3) 7 
 8 
Table 3 – Augmented category 6 connecting hardware insertion loss 9 
 10 
Frequency 
(MHz) 
Insertion loss 
(dB) 
1.00 0.02 
4.00 0.04 
8.00 0.06 
10.00 0.06 
16.00 0.08 
20.00 0.09 
25.00 0.10 
31.25 0.11 
62.50 0.11 
100.00 0.16 
200.00 0.20 
250.00 0.28 
300.00 0.32 
400.00 0.35 
500.00 0.40 
 11 
12 
04/06/06 SP-3-4426-AD10-B, draft 4.0 (to be published asTIA/EIA-568-B.2-10) 
8 
7.1.3 Cabling insertion loss 1 
7.1.3.1 Channel insertion loss 2 
For all frequencies from 1 MHz to 500 MHz, when measured according to the procedures in 3 
annex C of ANSI/TIA/EIA-568-B.2-1, the channel insertion loss shall meet the values determined 4 
using equation (4). For the purposes of field measurements, calculated channel limits that result in 5 
insertion loss values less than 3 dB revert to a requirement of 3 dB maximum (see 6 
ANSI/TIA/EIA-568-B.2-3). Insertion loss values in table 4 computed from equation (4) are provided 7 
for information. 8 
 9 
f
f
ffossInsertionL
channel
02.04)
2.0
01.08.1(05.1 ⋅+++≤
 dB (4) 10 
 11 
Equation (4) includes an ILD allowance that is given by equation (5) for all frequencies from 1 MHz 12 
to 500 MHz). 13 
 14 
)
2.0
01.08.1(03.0
100,
f
ffILD
mchannel
++≤ (5) 15 
Table 4 – Augmented category 6 channel insertion loss 16 
 17 
Frequency 
(MHz) 
Insertion loss 
(dB) 
1.00 2.2 
4.00 4.1 
8.00 5.7 
10.00 6.4 
16.00 8.1 
20.00 9.1 
25.00 10.2 
31.25 11.4 
62.50 16.3 
100.00 20.8 
200.00 30.0 
250.00 33.8 
300.00 37.3 
400.00 43.6 
500.00 49.3 
 18 
 19 
NOTES, 20 
1 The insertion loss of the channel does not take into consideration the 0.1 dB 21 
measurement floor of the connecting hardware insertion loss requirement. 22 
2 The channel insertion loss requirement is derived using the insertion loss contribution 23 
of 4 connections. 24 
 25 
26 
SP-3-4426-AD10-B, draft 4.0 (to be published as TIA/EIA-568-B.2-10) 04/06/06  
9 
7.1.3.2 Permanent link insertion loss 1 
For all frequencies from 1 MHz to 500 MHz, augmented category 6 permanent link insertion loss 2 
shall meet the values determined using equation (9). For the purposes of field measurements, 3 
calculated permanent link limits that result in insertion loss values less than 3 dB revert to a 4 
requirement of 3 dB maximum (see ANSI/TIA/EIA-568-B.2-3). The values in table 5 are provided 5 
for information only. 6 
∑
∑
+=
cableconnlinkperm
ossInsertionLossInsertionLossInsertionL
_
 7 
 8  
linkperm
ILD
_
+
 dB (6) 9 
where: 10 
 11 
mcablecable
ossInsertionLossInsertionL
100,
9.0 ⋅= dB, and (7) 12 
 13 
5.1
_
00015.0 fILD
linkperm
= dB (TBD – Editor: See TBD in equation (9) also) (8) 14 
 15 
 16 
 17 
)(00015.0
18.0
009.068.1
5.1
_
TBDf
f
ffossInsertionL
linkperm
+++≤ dB (9) 18 
 19 
Table 5 – Augmented category 6 permanent link insertion loss 20 
 21 
Frequency 
(MHz) 
Insertion loss 
(dB) 
1.00 1.9 
4.00 3.5 
8.00 4.9 
10.00 5.5 
16.00 6.9 
20.00 7.7 
25.00 8.7 
31.25 9.7 
62.50 13.9 
100.00 17.9 
200.00 26.0 
250.00 29.4 
300.00 32.6 
400.00 38.4 
500.00 43.8  
22 
 23 
NOTES, 24 
1 The insertion loss of the permanent link does not take into consideration the 0.1 dB 25 
measurement floor of the connecting hardware insertion loss requirement. 26 
2 The permanent link insertion loss requirement is derived using the insertion loss 27 
contribution of 3 connections. 28 
 29 
30 
04/06/06 SP-3-4426-AD10-B, draft 4.0 (to be published asTIA/EIA-568-B.2-10) 
10 
7.2 NEXT loss and PSNEXT loss 1 
NEXT loss is a measure of the unwanted signal coupling from a transmitter at the near-end into 2 
neighboring pairs measured at the near-end. NEXT loss is expressed in dB relative to the transmit 3 
signal level. NEXT loss shall be measured for all pair combinations of cables and cabling in 4 
accordance with annex C of ANSI/TIA/EIA-568-B.2 and the ASTM D 4566 NEXT loss 5 
measurement procedure. In addition, the test fixture shall provide for consistent common and 6 
differential mode impedance matching for the unjacketed twisted-pairs between the cable jacket 7 
and the balun terminations. Connecting hardware NEXT loss shall be measured for all pair 8 
combinations in accordance with annex G. Modular plug cord NEXT loss shall be measured for all 9 
pair combinations in accordance with annex . In addition, since each duplex channel can be 10 
disturbed by more than one duplex channel, power sum near-end crosstalk (PSNEXT) loss is also 11 
specified for cabling and cables. 12 
7.2.1 NEXT loss 13 
7.2.1.1 Cable NEXT loss 
14 
For all frequencies from 0.772 MHz to 500 MHz, augmented category 6 cable NEXT loss, for a 15 
length of 100 m (328 ft) or longer, shall meet the values determined using equation (10). The 16 
values in table 6 are provided for information only. 17 
 18 
)100/log(153.44 fNEXT
cable
−≥ dB (10) 19 
 20 
Table 6 - Augmented category 6 cable NEXT loss 21 
 22 
Frequency 
(MHz) 
NEXT loss 
(dB) 
0.150 86.7 
0.772 76.0 
1.00 74.3 
4.00 65.3 
8.00 60.8 
10.00 59.3 
16.00 56.2 
20.00 54.8 
25.00 53.3 
31.25 51.9 
62.50 47.4 
100.00 44.3 
200.00 39.8 
250.00 38.3 
300.00 37.1 
400.00 35.3 
500.00 33.8 
 23 
NOTE - 0.150 MHz is for reference purposes only. 24 
25 
SP-3-4426-AD10-B, draft 4.0 (to be published as TIA/EIA-568-B.2-10) 04/06/06  
11 
7.2.1.2 Connecting hardware NEXT loss 1 
For all frequencies from 1 MHz to 500 MHz, augmented category 6 connecting hardware NEXT 2 
loss shall meet the values determined using the equations specified in table 7 when mated to the 3 
range of test plugs specified in clause G.3. Calculations that result in NEXT loss values greater 4 
than 75 dB shall revert to a requirement of 75 dB minimum. The values in table 8 are provided for 5 
information only. 6 
 7 
Table 7 – Augmented category 6 connecting hardware NEXT loss 8 
 9 
Frequency 
(MHz) 
NEXT loss 
(dB) 
1 ≤ f ≤250 
250 < f ≤ 500 
54-20log(
f/100) 
46.04-40log(
f/250) 
 10 
Table 8 – Augmented category 6 connecting hardware NEXT loss 11 
 12 
Frequency 
(MHz) 
NEXT loss 
(dB) 
1.00 75.0 
4.00 75.0 
8.00 75.0 
10.00 74.0 
16.00 69.9 
20.00 68.0 
25.00 66.0 
31.25 64.1 
62.50 58.1 
100.00 54.0 
200.00 48.0 
250.00 46.0 
300.00 42.9 
400.00 37.9 
500.00 34.0 
 13 
14 
04/06/06 SP-3-4426-AD10-B, draft 4.0 (to be published asTIA/EIA-568-B.2-10) 
12 
7.2.1.3 Work area, equipment, and patch cord NEXT loss 1 
Work area, equipment, and patch cords shall meet the values determined using the equations of 2 
this clause. Modular plug cords shall be measured in accordance with annex . The measured 3 
NEXT loss of modular plug cords shall exceed the values calculated in equation (11). 4 
 5 
(
)
RFEXT
conn
IL
cable
NEXT
connectors
NEXT
limitcord
NEXT −
⋅+−
+
−
−=
10
2
10
10
10log10
_
 (11) 6 
where: 7 
(
)
(
)
++−
+
−
−=
20
2
10
20
10log20
conn
IL
cable
IL
conn
NEXT
conn
NEXT
connectors
NEXT
 (12) 8 
 9 
100
100,
hCableLengt
mcable
IL
IL
DeRating
cable
IL ⋅⋅=
 (13) 10 
⋅−
−−=
cable
IL
e
mcable
NEXT
cable
NEXT
46.0
1log10
100,
 (14) 11 
 12 
conn
NEXT
 is the mated NEXT loss assigned to the local and remote patch cord test adapter, in dB 13 
as shown specified in clause 7.2.1.2. 14 
where: 15 
f is the frequency in MHz, NEXT is in dB, and cable length is in meters. 16 
 17 
mcable
IL
100,
is the insertion loss of 100 meters of cable as specified in equation (1). 18 
 19 
I
L
Derating
is the de-rating factor specified for cable as specified in equation (2). 20 
 21 
conn
IL
is the insertion loss of a compliant connector as specified in equation (3). 22 
 23 
24 
SP-3-4426-AD10-B, draft 4.0 (to be published as TIA/EIA-568-B.2-10) 04/06/06  
13 
cable
NEXT
 is the cable NEXT loss computed from the NEXT loss requirements for 100 m cable, 1 
the insertion loss requirements for 100 m patch cable, the length correction formula in ASTM D 2 
4566, and 3 
 4 
mcable
NEXT
100,
is the NEXT loss test limit for 100 m cable as specified in equation (10). 5 
 6 
RFEXT is the allowance for reflected FEXT loss as described in equation (15). 7 
 8 
RFEXT = 0.5 dB (15) 9 
 10 
 11 
The low frequency measurement plateau for connector insertion loss and connector NEXT loss do 12 
not apply to the calculation of cord limits. Calculations that result in NEXT loss greater than 65 dB 13 
shall revert to a limit of 65 dB. The values in table 9 are provided for information only. 14 
Table 9 - Example augmented category 6 work area, equipment, and patch cord NEXT loss 15 
limits 16 
Frequency 
(MHz) 
1 m cord limit
(dB) 
2 m cord limit
(dB) 
5 m cord limit
(dB) 
10 m cord limit 
(dB) 
1.00 65.0 65.0 65.0 65.0 
4.00 65.0 65.0 65.0 65.0 
8.00 65.0 65.0 65.0 64.8 
10.00 65.0 65.0 64.5 63.0 
16.00 62.7 62.0 60.5 59.1 
20.00 60.7 60.1 58.7 57.3 
25.00 58.8 58.2 56.8 55.4 
31.25 56.9 56.3 54.9 53.6 
62.50 51.0 50.4 49.2 48.1 
100.00 47.0 46.4 45.4 44.5 
200.00 41.1 40.7 39.9 39.3 
250.00 39.3 38.9 38.1 37.7 
300.00 36.4 36.2 35.9 35.8 
400.00 31.8 31.9 32.1 32.5 
500.00 28.2 28.4 29.0 29.8 
 17 
 18 
 19 
20 
04/06/06 SP-3-4426-AD10-B, draft 4.0 (to be published asTIA/EIA-568-B.2-10) 
14 
7.2.1.4 Channel NEXT loss 1 
For all frequencies from 1 MHz to 500 MHz, augmented category 6 channel NEXT loss shall meet 2 
the values determined using the equations in table 10. Calculations that result in NEXT loss values 3 
greater than 65 dB shall revert to a requirement of 65 dB minimum. The values in table 11 are 4 
provided for information only. 5 
 6 
Table 10 – Augmented category 6 channel NEXT loss 
 7 
Frequency 
(MHz) 
NEXT loss 
(dB)   
1 ≤ f < 330   
330 ≤ f ≤ 500 
)
20
))100/log(2054(
102
20
))100/log(153.44(
10log(20
ff
channel
NEXT
−
−
⋅+
−
−
−≥  
)330/log(15.2731 f
channel
NEXT
−
≥  
 8 
 9 
Table 11 – Augmented category 6 channel NEXT loss 10 
 11 
Frequency 
(MHz) 
NEXT loss 
(dB) 
1.00 65.0 
4.00 63.0 
8.00 58.2 
10.00 56.6 
16.00 53.2 
20.00 51.6 
25.00 50.0 
31.25 48.4 
62.50 43.4 
100.00 39.9 
200.00 34.8 
250.00 
300.00 
33.1 
31.7 
400.00 28.7 
500.00 26.1 
 12 
13 
SP-3-4426-AD10-B, draft 4.0 (to be published as TIA/EIA-568-B.2-10) 04/06/06  
15 
7.2.1.5 Permanent link NEXT loss 1 
For all frequencies from 1 MHz to 500 MHz, augmented category 6 permanent link NEXT loss shall 2 
meet the values determined using the equations in table 12. Calculations that result in NEXT loss 3 
values greater than 65 dB shall revert to a requirement of 65 dB minimum. The values in table 13 4 
are provided for information only. 5 
Table 12 – Augmented category 6 permanent link NEXT loss 
 6 
Frequency 
(MHz) 
NEXT loss 
(dB)   
1 ≤ f < 300   
300 ≤ f ≤ 500 
)
20
))100/log(2054(
10
20
))100/log(153.44(
10log(20
_
ff
NEXT
linkperm
−
−
+
−
−
−≥  
)300/log(13.3334
_
fNEXT
linkPerm
−
≥  
 7 
 8 
Table 13 – Augmented category 6 permanent link pair-to pair NEXT loss 9 
 10 
Frequency 
(MHz) 
NEXT loss 
(dB) 
1.00 65.0 
4.00 64.1 
8.00 59.4 
10.00 57.8 
16.00 54.6 
20.00 53.1 
25.00 51.5 
31.25 50.0 
62.50 45.1 
100.00 41.8 
200.00 36.9 
250.00 35.3 
300.00 34.0 
400.00 29.9 
500.00 26.7 
 11 
12