6FM230D-X

12V 230Ah(20hr)

The rechargeable batteries are lead-lead dioxide systems. The dilute sulfuric acid
electrolyte is absorbed by separators and plates and thus immobilized. Should the
battery be accidentally overcharged producing hydrogen and oxygen, special oneway valves allow the gases to escape thus avoiding excessive pressure build-up.
Otherwise, the battery is completely sealed and is, therefore, maintenance-free,
leak proof and usable in any position.
Battery Construction
Component

Positive plate

Negative plate

Container

Cover

Safety valve

Terminal

Separator

Electrolyte

Raw material

Lead dioxide



Lead

ABS

ABS

Rubber

Copper

Fiberglass

Sulfuric acid

General Features













Absorbent Glass Mat (AGM) technology

for efficient gas recombination of up to
99% and freedom from electrolyte
maintenance or water adding.
Not restricted for air transport-complies
with IATA/ICAO Special Provision A67.
UL-recognized component.
Can be mounted in any orientation.
Computer designed lead, calcium tin alloy
grid for high power density.
Long service life, float or cyclic
applications.
Maintenance-free operation.
Low self discharge.

Dimensions and Weight
Length(mm / inch)
Width(mm / inch)
Height(mm / inch)
Total Height(mm / inch)
Approx. Weight(Kg / lbs)

520 / 20.5
269 / 10.6
203 / 8.0
208 / 8.2
72.6 / 160.1

Performance Characteristics
Nominal Voltage
12V

Number of cell
6
Design Life
10 years
o
o
Nominal Capacity 77 F(25 C)
20 hour rate (11.5A, 10.8V)
230Ah
10 hour rate (21.0A, 10.8V)
210Ah
5 hour rate (40.3A, 10.5V)
201.5Ah
150Ah
1 hour rate (150A, 9.6V)
Internal Resistance
2.8mOhms
Fully Charged battery 77oF(25oC)
Self-Discharge
3% of capacity declined per month at 20oC(average)
Operating Temperature Range
Discharge
-20~60oC
Charge
-10~60oC
Storage
-20~60oC
o
o
1100A(5s)

Max. Discharge Current 77 F(25 C)
Short Circuit Current

4300A

Charge Methods: Constant Voltage Charge
Cycle use
Maximum charging current
Temperature compensation
Standby use
Temperature compensation

77oF(25oC)
2.30-2.35VPC
63A
-30mV/oC
2.23-2.27VPC
-20mV/oC

Discharge Constant Current (Amperes at 77oF25oC)
End Point
Volts/Cell

10min

15min

30min

45min


1h

3h

5h

10h

20h

1.60V

523

395

232

180

150

68.5

41.0

21.8

1.65V


506

384

231

176

147

68.2

40.8

21.6

9.9
10.2

1.70V

475

373

230

174


145

67.8

40.6

21.4

1.75V

442

362

226

172

144

66.8

40.3

21.2

10.6
11.1

1.80V


413

350

223

170

142

66.5

40.0

21.0

11.5

Discharge Constant Power (Watts at

77oF25oC)

End Point
Volts/Cell

10min

15min


30min

45min

1h

1.60V

930

640

439

341

1.65V

905

630

436

339

1.70V

870


624

432

1.75V

825

610

429

2h

3h

5h

286

172

131

86.7

284

171


130

86.4

327

280

169

129

86.1

325

278

168

128

85.8

1.80V
770
600
425
322
275

166
126
85.4
(Note)The above characteristics data are average values obtained within
three charge/discharge cycles not the mimimum values.

page1 of 2

www.vision-batt.com


O

Current

Charged
Volume

Discharge characteristic (25 C)

Voltage

6FM230D-X

Charge characteristic curve
Constant voltage charge characteristic
(0.25CA,25 oC)

(%) (XCA) (V)


12.0

12V230Ah

Battery voltage(V)

140

66.8A 40.3A
9.6

21.0A

120

0.25

100

0.20

80

215A 150A

440A

0.15

1


2

3

20 30

5
10
min

60

2

3

5

10

20

0.10

20

0.05

0


0

h

CHARGED VOLUME

14.0

CHARGE VOLTAGE

13.0

60
40

0

15.0

12.0
11.0

0

Discharge time

(V/8V)

(V/6V)


(V/4V)

(V/CELL)

7.8

5.2

2.6

15.0

10.0

7.5

5.0

2.5

14.4

9.6

7.2

4.8

2.4


9.2

6.9

4.6

2.3

13.2

8.8

6.6

4.4

2.2

CY

CL

ND B

EU

SE

12


14

16

18

20

Y US

12
14
16
18
Storage time: months

20

80
70
60

E

40 oC

30 oC

20 oC


50
0

10
20
30
40
50
Ambient temperature( oC)

40

60

0

2

4

6

8

10

Cycle service life in relation to
depth of discharge


Life characteristics of standby use
120

100

100
Capacity(%)

Capacity(%)

10

90

120

80
60

Testing conditions: floating voltage: 2.27 to 2.30V/Cell
ambient temperature: 25 oC(77 oF)

80
60

40

40

20


20

0

4

6
Life(year)

100% D.O.D.

0

8

200

30% Depth of discharge

50% D.O.D.

400

600

800

1000


1200

1400

1600

Number of cycles(cycles)

Temperature effects on float life

Temperature effects on capacity
120

15

100

C
0 .0 5
0 .1 C
0 .2 C

2.30V/Cell

10

Capacity (%)

Life(years)


8

100

-10

0

6

110

S TA

13.8

4

Self-discharge characteristic

Capacity(%)

(V/12V)

10.4

2

Charging time (hours)


Relationship between
charging voltage and temperature

15.6

CHARGING CURRENT

5

80
60

1.0C

40

2.0C

20
0

10

20

30

40

0


50

-20

-10

o

Temperature( C)

THE INTERNATIONAL CERTIFICATION NETWORK

ISO9001:2000

MH25860

0

10
20
Temperature( oC)

30

40

G4M19906-9202-E-16

www.vision-batt.com


Shenzhen Center Power Tech. Co., Ltd.
Center Power Industrial Park, Tongfu Industrial District Dapeng Town, 518120 Shenzhen, China
Tel: (+86-755) 8431 8088 Fax: (+86-755) 8431 8038 E-mail:
Copy Right Shenzhen Center Power Technology Co., Ltd (Edition 2011-8)

Page 2 of 2

50



×