Series HMI Connection Manual

Hướng dẫn kết nối PLC với HMI Delta DOP

Keyence KV1000
HMI Factory Setting:
Baud rate: 9600. 8. Even. (RS232)
Controller Station Number: 0 (no PLC station number in protocol, one on one connection)
Control Area / Status Area: DM-0/DM-10
Connection
a. RS-232 (DOP-A/AE/AS, DOP-B Series)
DOP series

Controller

9 pin D-sub male (RS-232)
RXD (2)

(5) SD

TXD (3)

(3) RD

GND (5)

(4) SG

Definition of PLC Read/Write Address
a. Registers
Type



Format
Word No. (n)

Read/Write Range

Data
Length

Data Memory

DM-n

DM-0 ~ DM-65535

Word

Control Memory

CM-n

CM-0 ~ CM-11999

Word

Temporary Data Memory

TM-n

TM-0 ~ TM-511


Word

Extended Data Memory

EM-n

EM-0 ~ EM-65535

Word

Extended Data Memory

FM-n

FM-0 ~ FM-32767

Word

Address Register

Z-n

Z-1 ~ Z-12

Word

Digital Trimmer

AT-n


AT-0 ~ AT-7

Word

High-speed Counter

CTH-n

CTH-0 ~ CTH-1

Double

Note

Word
CTC Preset Value

PCTC-n

PCTC-0 ~ PCTC-3

Double
Word

Timer Preset Value

PT-n

PT-0 ~ PT-3999


Double
Word

Counter Preset Value

PC-n

PC-0 ~ PC-3999

Double
Word

V1.01

Revision May, 2011

www.plc.today 71


Series HMI Connection Manual

Type
High-speed Counter

Format
Word No. (n)
CTC-n

Data

Length

Read/Write Range
CTC-0 ~ CTC-3

Double

Comparator
Timer

Note

Word
T-n

T-0 ~ T-3999

Double
Word

Counter

C-n

C-0 ~ C-3999

Double
Word

b. Contacts

Format
Type

Word No. (n)
Bit No. (b)

Read/Write Range

Control Relay

CR-nbb

CR-000 ~ CR-3915

Internal Memory Relay

MR-nbb

MR-000 ~ MR-99915

Latch

LR-nbb

LR-000 ~ LR-99915

Relay

R-nbb


R-000 ~ R-59915

High-speed Counter

CTC-b

CTC-0 ~ CTC-3

Timer Contact

T-b

T-0 ~ T-3999

Counter Contact

C-b

C-0 ~ C-3999

Note

comparator

72

V1.01

Revision May, 2011



Series HMI Connection Manual

Hướng dẫn kết nối PLC với HMI Delta DOP

Keyence KV/KZ Series
HMI Factory Setting:
Baud rate: 9600, 8, Even, 1 (RS-232)
Controller Station Number: 0 (no PLC station number in protocol, one on one connection)
Control Area / Status Area: DM-0 / DM-10

Connection
a. RS-232 (DOP-A, DOP-B Series)
KV Series (Note1)
DOP series

Controller

9 pin D-SUB (RS-232)

RJ-11 (RS-232)

RXD (2)

(5) SD

TXD (3)

(3) RD


GND (5)

(4) SG

KZ Series (Note1)
DOP series

Controller

9 pin D-SUB (RS-232)

RJ-11 (RS-232)

RXD (2)

(5) SD

TXD (3)

(3) RD

GND (5)

(4) SG

Definition of PLC Read/Write Address
a. Registers
Type

Format

Word No. (n)

Read/Write Range

Data
Length

Timer

T-n

T-0 – T-199

Word

Counter

C-n

C-0 – C-199

Word

High-speed counter

CTH-n

CTH-0 – CTH-1

Word


High-speed counter

CTC-n

CTC-0 – CTC-3

Word

Note

comparator
V1.01

Revision August, 2010

www.plc.today 73


Series HMI Connection Manual

Type

Format

Data
Length

Read/Write Range


Word No. (n)

Data memory

DM-n

DM-0 – DM-1999

Word

Temporary data memory

TM-n

TM-0 – TM-31

Word

Timer preset value

PT-n

PT-0 – PT-199

Word

Counter preset value

PC-n


PC-0 – PC-199

Word

CTC preset value

PCTC-n

PCTC-0 – PCTC-3

Word

Note

b. Contacts
Format
Type

Read/Write Range

Word No. (n)
Bit No. (b)

Note

Relay

R-nbb

R-000 – R-6915


Timer

T-b

T-0 – T-199

1

Counter

C-b

C-0 – C-199

1

CTC-b

CTC-0 – CTC-3

High-speed counter
comparator

NOTE
1)

Please be aware the pin definition of SD, RD is reversed in KZ-80T and KV series.
This protocol regards PLC protocol in KV series, when communicates with KZ series PLC,
the following divergence will occur.

1. Readable Timer address is not continuous. For example:
T-0 ~ T-9 can be read
T10 cannot be read
T11 ~ T20 can be read
T21 ~ T50 cannot be read …etc.
2. Counter cannot be read. For example:
Registers: C-, CTH-, CTC-,PC-, PCTC- all cannot be read.
Contacts: C-, CTC- cannot be read as well.

74

V1.01

Revision August, 2010



×