Tải bản đầy đủ (.pdf) (3 trang)

Hướng dẫn kết nối màn hình HMI delta với biến tần Fuji

Bạn đang xem bản rút gọn của tài liệu. Xem và tải ngay bản đầy đủ của tài liệu tại đây (121.62 KB, 3 trang )

Series HMI Connection Manual

Fuji Frenic Inverter
HMI Factory Setting:
Baud rate: 9600, 8, None, 2
Controller Station Number: 1(Note1)
Control Area / Status Area: None/None
Connection
a. RS-485 (DOP-A/AE Series)
DOP series

Controller

9 pin D-sub male (RS-485)
D- (1)
DXD- (4)
D+ (2)
DX+
D+ (3)

b. RS-485 (DOP-AS57 Series)
DOP series

Controller

Terminal Block

50

R+


DX+

R-

DX-

V1.00

Revision March, 2010


Series HMI Connection Manual

Hướng dẫn kết nối PLC với HMI Delta DOP

c. RS-485 (DOP-AS35/AS38 Series)
DOP series

Controller

Terminal Block (RS-485)
R- (1)
DXT- (4)
R+ (2)
DX+
T+ (3)

d. RS-485 (DOP-B Series)
DOP series


Controller

9 pin D-sub male (RS-485)
D+ (1)

DX+

D- (6)

DX-

Definition of PLC Read/Write Address
a. Registers
Type

Format
Word No. (n)

Read/Write Range

Data Length Note

Fundamental functions

Fn

F0 – F42

Word


Extension terminal

En

E1 – E47

Word

Cn

C1 – C33

Word

motor Parameters

Pn

P1 – P9

Word

High speed frequency

Hn

H3 – H39

Word


Alternative motor

An

A1 – A18

Word

Optional functions

On

O1 – O29

Word

Setting data function

Sn

S1 – S12

Word

Monitoring data functions

Mn

M1 – M48


Word

functions
Control functions of
frequency

parameters

V1.00

Revision March, 2010

www.plc.today 51


Series HMI Connection Manual

b. Contacts
Format
Type

Read/Write Range

Word No. (n)
Bit No. (b)

Fundamental functions

Fn.b


F0.0 – F42.15

Extension terminal

En.b

E1.0 – E47.15

Cn.b

C1.0 – C33.15

motor Parameters

Pn.b

P1.0 – P9.15

High speed frequency

Hn.b

H3.0 – H39.15

Alternative motor

An.b

A1.0 – A18.15


Optional functions

On.b

O1.0 – O29.15

Setting data function

Sn.b

S1.0 – S12.15

Monitoring data functions

Mn.b

M1.0 – M48.15

Note

functions
Control functions of
frequency

parameters

NOTE
1)

Controller Station Number range from 1 to 31, and Number 99 is for radio broadcast.


2)

Not all address is applicable to radio broadcast. Please refer to Fuji Frenic Inverter
manual for details on radio broadcast address.

3)

Not all address can be read and write. Please refer to Fuji Frenic Inverter manual for
details on read/ write characteristics.

52